Burkert Type 8035 User Manual

Page 117

Advertising
background image

115

Maintenanceandtroubleshooting

10.3.2 resolution of problems related to an error message and

the device state leD is red

Device
state
leD

output
Do4

output
Do1 and/or
Do2 and/
or Do3

message
displayed

possible cause

recommended action

red

0 Hz

not
switched

"PWRFAIL"

The supply voltage is too
low.

The device does not
function.

Check that the supply voltage
is between 12 and 36 V DC.

If the problem occurs again,
take contact with the retailer.

red

0 Hz

"ERROR3"

The user parameters are
lost.

Start the device again.

If the message persists, con-
figure the device again.

If the problem occurs again,
take contact with the retailer.

red

10 Hz

1)

"ERROR4"

The totalizer values are
lost.

The values saved upon the
next to last power down
are retrieved.

Start the device again.

If the problem occurs again,
take contact with the retailer.

red

0 Hz

"ERROR5"

Both "ERROR3" and
"ERROR4".

Start the device again.

If the message persists, con-
figure the device again.

If the problem occurs again,
take contact with the retailer.

red

10 Hz

1)

"ERROR6"

Totalizers definitely lost.

The totalizers are reset.

Start the device again.

If the problem occurs again,
take contact with the retailer.

red

0 Hz

"ERROR7"

Both "ERROR3" and
"ERROR6".

Start the device again.

If the message persists, con-
figure the device again.

If the problem occurs again,
take contact with the retailer.

red

10 Hz

1)

dosing being
done...

The rotational frequency
of the paddle wheel is >
2,2 kHz.

Check the flow rate in the
pipe.

If necessary, adjust the flow
rate.

If the problem occurs again,
take contact with the retailer.

1)

If parameter "ERR. 10HZ" is set to "ACTIVE". See chap. “9.7.26”.