Sensor type – Burkert Type 8035 User Manual

Page 41

Advertising
background image

39

Installationandwiring

Before connecting the flow sensor to the dosing controller 8025 Batch, in a panel-mounted or a wall-
mounted version:

• Set selector "SENSOR TYPE" depending on the output signal originating from the flow sensor. See

“Figure 29” and “Table 5”, page 40.

• If selector "SENSOR TYPE" is set on "NPN/PNP", set selector "SENSOR SUPPLY" depending on the

dosing controller supply voltage. See “Figure 30” and “Table 5”, page 40.

• Set selector "LOAD" depending on the type of signal sent out by the flow sensor and on the load

wanted on terminal 1 "PULSE INPUT" of terminal block "FLOW SENSOR". See “Table 5”, page 40.

Selector C makes it possible to configure the type of signal the 8025 Batch, panel- or wall-mounted version,
receives from the remote flow sensor.

→

Set the selector on the right (default position) when
the signal from the flow sensor which is connected to
the 8025 Batch is either:

• a pulse signal, NPN or PNP

• an "on/off" signal (Reed relay for example)

• a 0-5 V DC standard voltage signal (TTL, for example)

→

Set the selector on the left when the
signal from the flow sensor which is
connected to the 8025 Batch is a sine-
wave signal (coil).

C

SENSOR TYPE

COIL

NPN/PNP

SENSOR TYPE

COIL

NPN/PNP

Figure 29:

Using selector "SENSOR TYPE" on a panel- or wall-mounted version

When selector "SENSOR TYPE" above
is set on "NPN/PNP", selector A
makes it possible to configure the supply
voltage for the remote flow sensor.

SENSOR

SUPP

LY

+5V

L+

(L+)-12V

A

→

If the device is energized with a 115/230 V AC power supply, set
selector "SENSOR SUPPLY" on "L+" (default position).

→

If the device is energized with a 12-36 V DC power supply, set
the voltage selector "SENSOR SUPPLY" depending on the
voltage supply needed by the remote flow sensor: "+5V", "L+" or
"(L+)-12V" (default position).

Figure 30:

Using selector "SENSOR SUPPLY" on a panel- or wall-mounted version