Respect the following additional mounting conditions to ensure that the measuring device operates correctly:

- Ensure that the pipe is always filled in the section around the device (see Figure 9).

- When mounting vertically ensure that the flow direction is in an upward direction (see Figure 9).

Horizontal mounting

Correct

Incorrect

Vertical mounting

Correct

Incorrect

flow direction

Figure 9:

Filling of the pipe

→

If necessary, use a flow conditioner to improve measurement precision.

7.2.2

installation onto the pipe

1

2

3

5

4

6

→

Install the S020 fitting into the pipe taking into account the recommendations in
chap. “7.2.1”.

→

Check that there is a seal on the fitting and that it is not damaged. Replace the seal
if necessary.

→

Check that there is a seal (mark 6) on the flow sensor.

→

Insert the nut (mark 3) on the fitting.

→

Insert the snap ring (mark 2) into the groove (mark 5).

→

Position the device in order the arrow on the side of the housing indicates the direction
of the flow. The totalizers will increment.

→

Insert the device (mark 1) into the fitting.

→

Tighten the nut (mark 3) by hand on the device.

Figure 10:

Installation of a 8025 Batch, compact version, into an S020 fitting

7.3

installation of a panel version

install the panel version of the device in a cabinet with a protection class at least ip54 to ensure a
degree of pollution 2 inside the cabinet.