118

Maintenanceandtroubleshooting

Device
state leD

output Do1
and/or Do2
and/or Do3

output Do4
in "stAte"
mode

message
displayed

possible cause

recommended action

orange,
3,5 Hz
flashing

Switched

2)

3,5 Hz-fre-
quency

"ERROR [T]" The message

can only appear
if the dosing
mode "EXT. [T]" is
active.

The dosing
quantity is
exceeded when
the input DI1 has
been deactivated.

→

Increase the values of the
parameters A and B in order
to reduce the activation time of
the digital input DI1 and so that
"A*T + B" < flow rate times T.

→

or set a time delay before
the valves open. See chap.
“9.7.24” and “9.7.25”.

→

or reduce the flow rate in the
pipe.

→

Confirm the message by
pressing the key "ENTER" or
by sending out a pulse on DI4:
the current dosing is aborted.

orange,
3,5 Hz
flashing

Switched

2)

3,5 Hz-fre-
quency

"ERROR [T]" The message

can only appear
if the dosing
mode "EXT. [T]" is
active.

The dosing
quantity, deter-
mined by the
device depending
on the activation
duration of the
digital input DI1,
has exceeded
the required
thresholds.

→

Set the values of the param-
eters A and B and the value
of the activation duration T so
that "A*T+B" < 100 000 and
"A*T+B" times the K factor
of the fitting used is higher or
equal to 6.

→

Set an activation duration
T < 300 s.

→

Confirm the message by
pressing the key "ENTER" or
by sending out a pulse on DI4:
the current dosing is aborted.

2)

If the output is configured to switch when an alarm is generated. See chap. “9.7.18”.

English

Type 8025 - 8035 BATCH