STEP 7

Programming Current Sensing

The 835/836 control boards incorporate a safety feature that will put the op-
erator into a hard shutdown mode if the control board detects a current sense
two consecutive times during a cycle. This hard shutdown condition can only
be reset by shorting the FIREBOX or UL connectors on the left side of the
control board to ground. This condition may also be reset by pressing the
HARD SHUTDOWN RESET button located toward the upper right hand cor-
ner of the control board. If a firebox is used in the installation, The firebox
door (optional) should be opened and closed to reset the control board.

The following instructions must be followed at installation for proper safety assurance.
All limits should be set before beginning this procedure.

This new procedure applies to revision 31 or higher firmware.

1. Press and hold the LED ENABLE button for five seconds. The STOP LED will blink
indicating that the board is in learn mode.

3. Cycle gate for 3 full cycles. The STOP LED will stop blinking indicating that the board
is now ready for normal operation

4. Test the auto reverse sensitivity to ensure maximum safety protection. The current
sensitivity adjustment pot may be adjusted to decrease or increase sensitivity.

8. Refer to the 835/836 Operator Control Board Manual to set other options such as
program switch options and close timer adjustments.

Installation is now complete.

Note: Program switch #9 is no longer functional and the current sense may be readjusted

at any time.

CLOCKWISE

Less sensitivity

Gate is harder to
current sense

COUNTER CLOCKWISE

More sensitivity

Gate is easy to current
sense