53IT5100B Indicator/Totalizer

INSTRUCTION MANUAL

Table 4-2. Database Modules

Item Title

Purpose

See

Table

1

Analog Input Module

This module is used to configure the voltage input
characteristics (e.g., input voltage range) and how the input
signal is interpreted (linear or square root representation).

4-3

2

Analog Output Module

The primary purpose of this module is to set the 0 - 20 mA
output signal relative to the displayed percent output.

4-4

3

Contact Input Module This module allows the action of the CCIs to be reversed

(normally a closed contact = 1, but can be change to = 0).

4-5

4

Contact Output
Module

This module allows the action of a CCOs to be reversed
(normally a closed contact = 1, but can be changed to = 0).

4-6

5

Alarm Module

The primary purpose of this module is to set the instrument’s
Alarm Index mode, Alarm Limits 1 & 2, and Alarm Dead
Band.

4-7

6

Totalizer Module

The totalizers provide the sum of each analog input (ANI0-3).
This module is used to set input scaling factors, rollover and
dropout values, and to define display tags for each totalizer.

4-8

7

Communication
Module

This module is used to configure the Datalink port
parameters (e.g., baud rate, parity selection, etc.).

4-9

8

System Module

This module is used to set the instrument tag name and the
display brightness.

4-10