Table 4-5. contact input module (cci) – Micromod Micro-DCI: 53IT5100B Micro-DCI 4-Channel Indicator Totalizer User Manual

Page 38

Advertising
background image

53IT5100B Indicator/Totalizer

INSTRUCTION MANUAL

Table 4-5. Contact Input Module (CCI)

Purpose: This module allows the action of the CCIs to be reversed (normally a closed contact = 1, but can be
changed to = 0).

Title

Symbol

CCI

Datapoin

t

Default

Attribute

Contact
Input
(Display
Only)

CCI0
CCI1

CCI0
CCI1

L000
L001

0
0

When open, a 4 -24 V dc input signal = 0 when IINV =
0.
When open, a 4 -24 V dc input signal = 1 when IINV =
1.
When closed, a < 1 V dc input signal = 1 when IINV = 0.
When closed, a < 1 V dc input signal = 0 when IINV = 1.

Contact
Input
Invert

IINV0
IINV1

CCI0
CCI1

L264
L265

0 0

As shown above, it reverses the action of the CCI
datapoint.

Display
Message

CCI0

CCI1

A055
A056

ALARM A
ALARM B

The messages for CCI0 and CCI1, respectively, on the
Alarm Summary display.

Tag
Name

CITAG0
CITAG1

CCI0
CCI1

A262
A263

CCI-0
CCI-1

It is an assignable 10 character name for the contact
control input.

Display
Mode

SMA
SMB

CCI0
CCI1

L352
L353

0 0

Alarm
Enable

SAA
SAB

CCI0
CCI1

L368
L369

0 0

Display Mode, Alarm Enable, and Contact Input interact
to alter the two five character segments of the Display
Messages (A055 and A056) as shown in the table that
follows:


Alarm Enable = 0

Alarm Enable = 1

Contact Input =

0 1 0

1

Display Mode

= 0

10 character
message.

10 character
message in
reverse video.

10 character
message.

No message blinking and no Alarm Banner blinking.

10 character message blinking in
reverse video with Alarm Banner
also blinking. (After pressing
Mode push button, 10 character
message appears in reverse
video.)

Display Mode

= 1

Frst half (5
characters) of 10
character
message
sequence.

Second half (5
characters) of
10 character
message
sequence.

First half (5
characters) of
10 character
message
sequence.

No message blinking and no Alarm Banner blinking.

Second half (5 characters) of 10
character message blinking with
Alarm Banner blinking. (After
pressing Mode push button, 5
character message remains, but
stops blinking.)

34

Advertising