53IT5100B Indicator/Totalizer

INSTRUCTION MANUAL

Table 4-7. Alarm Module

Purpose: The primary purpose of this module is to set the instrument’s Alarm Index mode, Alarm
Limits 1 & 2, and Alarm Dead Band.
Title

Symbol

CCO

Data-point Default Attribute

Alarm
Index

AIX0
AIX1
AIX2
AIX3

ALRM
0
ALRM
1
ALRM
2

ALRM

3

B335
B340
B345
B350

1
1
1
1

This parameter defines the Alarm Active (PA1 &
PA2) interpretation of the two Alarm Limits (PL1
& PL2). It is entered into the datapoint as an
index value (0-5 ) as follows (n = 0-3 and
correlates with ALRM0 through ALRM3):
0 PA1n: high when PV> PL1n

PA2n: low when PV< PL2n

1 None
2 PA1n: high when PV> PL1n

PA2n: not affected

3 PA1n: not affected

PA2n: low when PV< PL1n

4 PA1n: high when PV> PL1n

PA2n: hi-hi when PV> PL2n

5 PA1n: low when PV< PL1n

PA2n: lo-lo when PV< PL2n

Examples are provided as follows:

Alarm Examples:

B335 PV PL1

(C103)

PL2 (C104)

Alarm Notes

0

>60

60

high

Alarm Llimit 1 is set for 60: PV > 60 = high Alarm.

0

<40

40

low

Alarm Limit 2 is set for 40: PV < 40 = low Alarm.

2

>60

60

high

Alarm Limit 1 is set for 60: PV > 60 = high Alarm.

2

<40

40

N/A

Alarm Limit 2 is set for 40: PV < 40 = no alarm.

3

>60

60

N/A

Alarm Limit 1 is set for 60: PV > 60 = no alarm.

3 <40 40 Low

low Alarm Limit 2 is set for 40: PV < 40 = low
Alarm.

4

>60

60

high

Alarm Limit 1 is set for 60: PV > 60 = high Alarm.

4

<70

70

hi-hi

Alarm Limit 2 is set for 70: PV > 70 = hi-hi Alarm.

5

>40

40

low

Alarm Limit 1 is set for 40: PV < 40 = low Alarm.

5

<30

30

low-low Alarm Limit 2 is set for 30: PV < 30 = lo-lo Alarm.

36