53IT5100B Indicator/Totalizer

INSTRUCTION MANUAL

33

Table 4-4. Analog Output (ANO) Module

Purpose: The primary purpose of this module is to set the 0 - 20 mA output signal relative to the
displayed percent and to select the analog input signal (ANI0-3) that is to be routed to the analog
output (ANO0).
Title

Symbol

ANO0

Datapoint

Default Attribute

Analog Output
(Display Only)

ANO0

C000

0

The value in this datapoint represents the
percent of output to be generated by hardware
(e.g., 100% output = 20 mA).

Analog Output
Source

B100

0

This parameter determines which analog input
(ANI0-3) is routed to the analog output (ANO0).
The routing index values are as follows: 0 =
ANI0 →ANO0, 1 = ANI1 →ANO0 2 = ANI2
→ANO0, 3 = ANI3 →ANO0

0 -20 mA
Output

OZBASE0

L472

0

When a 0, the percentage output generates a 4
-20 mA signal. When set to 1 , the percentage
output generates a 0 -20 mA signal.

Calibrate Zero

COZ0

B267

Calibrate
Span

COS0

C300

These parameters are factory set and should
not need adjustment
under normal operation.
See Section 5.3 for adjustment.

Tag Name

AOTAG0

A244

ANO0 The assignable 10 character name for ANO0.



Figure 4-3. CCI0/1

Figure

4-4.

CCO0/1

NOTE: These figures are graphical representations of the signal conditioning that occurs on the

instrument main board. They are provided for reference purposes only.