Table 5-4. analog input modules (ai0-8) – Micromod Micro-DCI: 53MC5000 Multi-Loop Process Controller Instruction Manual User Manual
Page 151

Table 5-4. Analog Input Modules (AI0-8)
Title
Definition
Atom
AI0
AI1
AI2
AI3
AI4
AI5
AI6
AI7
AI8
Default
Square Root
Signal
This value specifies the
characteristics of the signaling input
as either linear or square root.
0 - Linear
1 - Square Root
When square root is selected, input
signals less than 1% after
linearization (10% input range)
force the input to its zero value.
SQRT
(0-8)
L440
L441
L442
L443
L444
L445
L446
L447 L448
0
Calibrate
Zero
This is the calibration zero
adjustment. This parameter
is
factory set and should not need
adjustment under normal
operation. See Section 18.4 for
additional information.
CIZ
(0-8)
B263
B264 B265
B266
Calibrate
Span
This is the calibration span
adjustment. This parameter
is
factory set and should not need
adjustment under normal
operation. See Section 18.4 for
additional information.
CIS
(0-8)
C296
C297 C298
C299
Frequency
Input
This specifies whether the signaling
input is a voltage or frequency.
0 - Voltage
1 - Frequency
The value of the input becomes
(Span X Freq) + Zero
See Section 1, Specifications, for
duty cycle input requirements.
FREQ
(0-8)
L468
L469
L470
L471
0