3.12.4 CONFIGURE A DATAPOINT

The following procedure illustrates how to alter the contents of datapoint C115 (CONTROL module &
Span parameter) from 100 to 200.

3.12.4.1 Procedure to Configure a Datapoint

•

Press the Mode button to enter the ENGINEER
mode indicated by the appearance of either CONFIG-
URE
, DISPLAY or PROGRAM at the bottom of the
display.

•

If CONFIGURE does not appear, press F2 until CON-
FIGURE
appears at the bottom of the display.

•

When CONFIGURE is displayed at the bottom, press
F3.

•

If using the Hi-Res display, as shown, press F2 until
DATAPOINT appears at the bottom of the display.

•

Then press F3 to enter DATAPOINT mode.

•

The screen should now show the point-entry line similar
to the one at the right.

•

Press the key until the character "C" appears on
the entry line.

•

Press the key to shift the first entry one position to
the left.

•

Press the key until "1" appears on the entry line.

•

Press the key to shift this entry one position to the
left.

•

Press the key until "1" appears on the entry line.

•

Press the key to shift this entry one position to the
left.

•

Press the key until "5" appears on the entry line.

•

The entry line should appear similar to that shown on
the right.

•

Press F3.

53MC5000 Process Control Station

3-14