Table 11-3. CS20 Two Loop Controller Datapoints
Data-
point
Table
Module
Title and Function
De-
fault
Setpoint Related Datapoints (Loop 1, Loop 2) (Cont)
C117,
C153
5-9
CON0,
CON1
Setpoint Slew Rate - It is a rate limit applied to the setpoint.
When configured to a non-zero value, the setpoint used in
the PID algorithm is only allowed to change by this amount
each scan time. The final value of the setpoint always
appears on the units display. A zero disables setpoint
slewing.
0
Miscellaneous Datapoints (Loop 1, Loop 2)
A000,
A002
5-9
CON0,
CON1
Tagname - Assignable 10 character name.
CON-
0, 1
A001,
A003
5-9
CON0,
CON1
Engineering Units - Assignable 10 character designator.
(Engineering Units appear on the Single Loop CON0 and
Single Loop CON1 displays only.)
PER-
CENT
L109,
L133
5-9
CON0,
CON1
Reverse Valve - Bottom of display loop output valve action
indicators: 1 = [O] [C] display order, 0 = [C] [O] display
order. (Reverse Valve indicators appear on the Single Loop
CON0 and Single Loop CON1 displays only.)
0
6 of 6
Section 11. CS20 - Two Loop Controller
11-11