9 controller modules (con0-3), Table 5-9. controller modules (con0-3) – Micromod Micro-DCI: 53MC5000 Multi-Loop Process Controller Instruction Manual User Manual
Page 159

5.9 CONTROLLER MODULES (CON0-3)
These modules affect the action of the control algorithms, the control loop displays, and control related functions (e.g., Auto Enable, etc.).
There are four Controller Modules (CON0-3) that can be configured separately, one for each control loop display. The number of control
loops provided by a controller is model number dependent.
Table 5-9. Controller Modules (CON0-3)
Title
Definition
Atom
CON0
CON1
CON2
CON3
Default
Control Alarm Mode
This parameter specifies the Alarm action (PA1
& PA2) of the two Alarm Limits (PL1 & PL2):
0 - H/L PA1: High when PV> PL1
PA2: Low when PV< PL2
1 - OFF - None
2 - H/- PA1: High when PV> PL1
PA2: not affected
3 - -/L PA1: not affected
PA2: Low when PV< PL1
4 - H/HH PA1: High when PV> PL1
PA2: Hi-Hi when PV> PL2
5 - L/LL PA1: Low when PV< PL1
PA2: Lo-Lo when PV< PL2
6 - DEV PA1: Hi-Dev when Dev > PL1
PA2: Lo-Dev when Dev < PL2
(Examples are in the cell that follows.)
AIX
(0-3)
B335
B340
B345
B350
1
1 of 9
5-
1
4
53
MC
50
00
P
ro
c
es
s
Co
nt
ro
l S
ta
ti
o
n