Micromod Micro-DCI: 53MC5000 Multi-Loop Process Controller Instruction Manual User Manual
Page 31

Table 1-5. OPTO 22 Module Specifications for 16DI/DO ITB
OPTO 22 DC Input Modules (Cont)
OPTO 22
Part Number
16DI/DO
Voltage
Input Voltage Range
Input
Current @
Max V In
Input
Maximum
for No Output
G41DC5G
5 V dc
35 - 60 V dc
6 mA
9 V dc
G41AC5
5 V dc
90 - 140 V dc
11 mA
45 V dc
G41AC5A
5 V dc
180 - 280 V dc
6.5 mA
80 V dc
G41DC24
24 V dc
10 - 32 V dc
25 mA
3 V dc
G41AC24
24 V dc
90 - 140 V dc
11 mA
45 V dc
OPTO 22 DC Output Modules
OPTO 22
Part Number
16DI/DO
Voltage
Output Line
Voltage
Range
Load
Current
@ 45
°
C
Load
Current
@ 70
°
C
Maximum
Off State
Leakage
G40DC5
5 V dc
5 - 60 V dc
3 Amps
2 Amps
1 mA
G40DC5A
5 V dc
5 - 200 V dc
1 Amp
0.55 Amp
2 mA
G40DC24
24 V dc
5 - 60 V dc
3 Amps
2 Amps
1 mA
Table 1-6. Single Channel Analog Input Option (AI8) Specifications
Item
Specification(s)
This option requires one of the 5B series isolation modules described in Table 1-8.
Safety classification
FM Approved: Nonincendive for Class 1, Div. 2, Group A,
B, C, & D hazardous locations.
Quantity
1 (Analog Input 8 - AI8).
Analog-to-digital specifications:
Accuracy
Resolution
±
0.1% Full Scale
12 bits
2 of 2
Section 1. Introduction
1-17