Table 9-3. CS4 Automatic/Manual Station Datapoints
Data-
point
Table
Module
Title and Function
De-
fault
Alarms Related Datapoints
B335
5-9
CON0
Control Alarm Mode - Used to select one of six alarm types
or none. See Table 5-9 for details and examples.
1
C103
5-9
CON0
Alarm Limit 1 - Point in engineering units where an alarm is
triggered because the Alarmed Variable is not within the limit
value set in C103.
100
C104
5-9
CON0
Alarm Limit 2 - Point in engineering units where an alarm is
triggered because the Alarmed Variable is not within the limit
value set in C104.
0
C105
5-9
CON0
Alarm Dead Band - Sets the activation/deactivation gaps for
the alarm limit points. It is in engineering units.
2
Miscellaneous Datapoints
A000
5-9
CON0
Tagname - Assignable 10 character name.
CON-
0
A001
5-9
CON0
Engineering Units - Assignable 10 character designator.
PER-
CENT
3 of 3
Section 9. CS4 - Automatic/Manual Station