Batch Accumulate

The Batch Accumulate function allows you to opt to have any

extra input pulses received in the multiply mode accumulate up to

a maximum batch of 999. If Batch Accumulate is enabled and

a pulse is received during the countdown, the programmed

multiply value will be added to the current displayed value. Pulses

causing the maximum batch of 999 to be exceeded will result in

an E4 error message. When Batch Accumulate is enabled, the

LCD screen alternates between the current multiply value and

"ACC"

EXT

X

. The Batch Accumulate function is activated

in the Setup Menu (see Section 13).

12.3 Programming the mA Response

The HH9 pump accepts a 0-20 mA or 4-20 mA signal directly. The

response to this signal is fully programmable. In the mA mode, the

pump speed is determined by the programmed response curve, as

defined by points "P1" and "P2." The factory default set values for

P1 and P2 are (4 mA, 0 SPM) and (20 mA, 100 SPM) respectively.

This is illustrated in Figure 12.

While in the mA mode, the pump speed

MIN

mA EXT

and the mA value

mA

are displayed alternately every four (4) seconds while the

pump is running.