INSTALLATION

RLN-IOM-2012-1205

SECTION 2

2-4

TABLE 1A - OPERATING REQUIREMENTS

Reliance Model Size

500

750

1000

1500

2000

2500

3000

Fuel Type

Natural Gas or Propane*

Input BTU/Hr Max
Min

500,000

750,000

1,000,000

1,500,000

2,000,000

2,500,000

3,000,000

100,000

150,000

200,000

300,000

400,000

500,000

600,000

Electrical Requirements (Amps) (120V/60/1)
(240V/60/3)

<3

NA

<3

NA

<3

NA

<6

NA

<6

NA

NA

<10

NA

<10

Water Content Gal
Liter

2.7

3

3

7.3

7.3

11

11

10.2

11.4

11.4

27.6

27.6

41.6

41.6

Dry Weight LB
KG

675

700

700

1000

1000

1400

1400

306

318

318

454

454

635

635

Operating Weight LB
KG

700

725

725

1060

1060

1492

1492

317.5

329

329

481

481

676.75

676.75

Anchor Bolt Size IN
MM

.75

.75

.75

.75

.75

.75

.75

19

19

19

19

19

19

19

Dimensions • Reliance Hydronic Boiler

Reliance Model Size

500

750 & 1000

1500 & 2000

2500 & 3000

A. Boiler Width

IN

24

24

32.125

34

MM

610

609.6

815.9

863.6

B. Boiler Height

IN

45

50.7

67.9

72

MM

1143

1287.8

1724.6

1828.8

C. Boiler Depth

IN

29.3

29.3

34.3

42.2

MM

744.2

744.2

871.2

1071.8

D. Boiler Depth with Trim

IN

43.9

43.9

49.3

55.9

MM

1115

1115

1115

1419.8

E. Air Inlet Diameter

IN

4

6

8

10

MM

101.6

152.4

203.2

254

F. Flue Outlet Diameter

IN

4

6

8

10

MM

101.6

152.4

203.2

254

G. Water Inlet/Outlet Size

IN

2

2

2.5

3

MM

50.8

50.8

63.5

76.2

H. Min Clearance to Walls

IN

1

1

1

1

MM

25.4

25.4

25.4

25.4

I. Min Clearance to Front and Rear

IN

36

36

36

36

MM

914.4

914.4

914.4

914.4

J. Min Clearance to Ceiling

IN

24

24

24

24

MM

609.6

609.6

609.6

609.6

TABLE 1B - BOILER DIMENSIONS (REFER TO FIGURE 1)

Notes:

Specifi cations and dimensions are approximate. We reserve the right to change specifi cations and dimensions without notice.

*The use of propane is allowable with concentration of up to 5% propylene, commonly referred to as HD5. The use of off -standard grades of propane,

such as propane HD10 (10% propylene) is not permitted unless a system is in place to reduce propylene concentration to less than 5% prior to

reaching any fuel delivery piping. This is the responsibility of the customer. Verify propylene concentration with supplier prior to commissioning and

operation of equipment.