Operation – Fulton Reliance (RLN) High Efficiency Cooper Fin Boiler User Manual

Page 41

Advertising
background image

Questions? Call (315) 298-5121, or visit us online at www.fulton.com

SECTION 3

RLN-IOM-2012-1205

OPERATION

3-11

Central Heat Confi guration (Setpoint) – (See Figure 20) The highest water
temperature the boiler will try to maintain in relation to the to the Minimum
Outdoor Temperature

Time of Day Setpoint – Forces the Outdoor Reset line to parallel shift down
to a lower setpoint, also known as a night time setback. A contact closure is
required on connector J10 terminals (2&3) to utilize Time of Day setpoint.

Example (See Figure 21): If the outdoor temperature is at 20 degrees Fahrenheit
the boiler temperature will be 172 degrees Fahrenheit. The boiler will modulate
to maintain this temperature and shutdown at 172 plus off Hysteresis, which from
the above Central Heat Confi guration Screen is 10, so the unit would shut down
at 172F +10 (Off Hysteresis) = 182 degrees. The boiler will get a call for heat at
172F+/- 10 (On Hysteresis) = 162.

FIGURE 20 - CENTRAL HEAT CONFIGURATION SETPOINT

FIGURE 21 - EXAMPLE SCREEN

!

WARNING

Non-Fulton product information is for
reference purposes only. No Fulton
document should substitute for full review
of documentation available from the
component manufacturer.

4

CAUTION

Only factory-trained personnel should
attempt to alter password protected Control
preset values.