Questions? Call (315) 298-5121, or visit us online at www.fulton.com

SECTION 2

RLN-IOM-2012-1205

INSTALLATION

2-13

4. The boiler must be disconnected at the boiler manual

shutoff valve (located at the end of the supplied gas
train) from the gas supply piping system during any
pressure testing of the system at pressures in excess of
1/2 psig (14 inch W.C.).

5. Gas piping must be installed in accordance with

National Fuel Gas Code, ANSI Z223.1 1991 or latest
addenda and any other local codes, which may apply.

6. The pipe and the fi ttings used must be new and free of

dirt or other deposits.

7. Piping must be of the proper size to ensure adequate

gas supply. A drip leg and union connection must be

installed upstream of the gas safety shut off valves.

8. Connect gas supply line to the open end of the tee on

which the drip leg is installed.

9. When making gas-piping joints, use a sealing

compound resistant to liquefi ed petroleum gases. Do
not use Tefl on tape on gas line threads.

10. After gas piping is completed and before wiring

installation is started, carefully check all piping
connections, (factory and fi eld), for gas leaks. Use a soap
and water solution.

Install Condensate Drain (Optional)

A condensate drain kit (Figure 8) is intended for use with the
Fulton Reliance boiler.

The Condensate Drain is Fulton Model Part Number 4-57-
000440. Its recommended Operating Temp. is 175 F max;
capacity is 4 QT; Inlet Size is 1inch; Outlet Size is 1 ½ inch;
Water Supply is 100 psi max.; and Max. Btu’s input per drain
kit is 12 MMBtu.

PH neutralization kits are available from the factory, if desired.

Adhere to the following for installation:

1. The 3/4” condensate drain on the Reliance unit must

be connected to the drain of the “Boot Tee” that must
be installed on the exhaust outlet of the boiler and
then tied together to the 1” inlet on the drain kit. One
or more drain lines may be connected to this inlet
(maximum of 12 MBH total per drain kit) through a
common header.

TABLE 3 - NOMINAL PIPE SIZE

Nominal
Pipe Size

ID

Equivalent Pipe
Length

Max Capacity in ft3 of natural gas per hour. Pressure drop of
0.5”wc/Equivalent length of pipe (feet)

(“)

(“)

90 Elb
(Feet)

Tee
(Feet)

20

40

60

80

100

150

200

1-1/4

1.380

3.45

6.9

950

-----

-----

-----

-----

-----

-----

1-1/2

1.610

4.02

8.04

1460

990

810

-----

-----

-----

-----

2

2.067

5.17

10.3

2750

1900

1520

1300

1150

950

800

2-1/2

2.469

6.16

12.3

4350

3000

2400

2050

1850

1500

1280

3

3.068

7.67

15.3

7700

5300

4300

3700

3250

2650

2280

4

4.026

10.1

20.2

15800

10900

8800

7500

6700

5500

4600

Ball Valve

Ball Valve

Gas Valve

Gas Inlet

FIGURE 7 - TYPICAL GAS TRAIN