Chapter 3 Communication

9

W i r i n g C o n f i g u r a t i o n

Wiring Setup FORM factor

4-wire WYE 3-element using 3 CTs

4Ln3

9S

4-wire WYE 3-element connection using 3 PTs, 3 CTs

4Ln3

9S

4-wire 3-element delta using 3 CTs

4LL3

9S

4-wire 3-element delta connection using 3 PTs, 3 CTs

4LL3

9S

3-wire 2½-element Open Delta connection using 3 CTs

3OP3

5S/35S

3-wire 2½-element Open Delta connection using 2 PTs, 3 CTs 3OP3

5S/35S

3-wire 2-element Open Delta using 2 CTs

3OP2

4-wire WYE 2½-element connection using 3 CTs

3Ln3

6S/36S

4-wire WYE 2½-element connection using 2 PTs, 3 CTs

3Ln3

6S/36S

4-wire 2½-element delta connection using 2 PTs, 3 CTs

3LL3

T a b l e 1 : W i r i n g C o n f i g u r a t i o n

NOTE

In 4LN3 and 3LN3 wiring modes, the voltage readings for volt demands represent line-to-neutral
voltages; otherwise, they will be line-to-line voltages. The voltage waveforms and harmonics in
4LN3 and 3LN3 wiring modes represent line-to-neutral voltages; otherwise, they will be line-to-line
voltages

F i g u r e 8 : F o u r W i r e W Y E C o n n e c t i o n N o P T s U s i n g 3 C T s - W i r i n g S e t u p :

4 L n 3