Chapter 3 Communication

15

R e l a y O u t p u t s ( 6 R O – o p t i o n a l m o d u l e )

The 6RO module consists of: four FORM C (SSR) and two FORM A (EMR) relay outputs.

To install the 6RO module follow instructions:

7) Remove the plastic cover

8) Remove the body shield

9) Plug-in the module in the I/O slot and attach it to bracket using the two screws

10) Connect the 6RO cable and pass it through the device base window cables

11) Mount back the body shield

12) Mount back the plastic cover

The 6RO module is factory or Meter Shop plugged-in at the I/O slot

External control loads can be connected to the contacts relay as shown in Figures 18.

For ratings, see Appendix: Technical Specifications

F i g u r e 1 8 : 6 R O C o n n e c t i o n

A n al og Ou tp u ts (4 A O – op ti on al m od u l e)

The PowerSmart Socket PQM analog output (AO) expansion module provides:

4 optically isolated analog outputs with an internal power supply;

Options for 0-20mA, 4-20mA, 0-1mA, and ± 1mA output; 1-cycle update time.

To install the 4AO module follow instructions:

1) Remove the plastic cover
2) Remove the body shield
3) Set SW1 and SW2 for the proper Analog Output current according

to following table

Analog Output
Current

SW1
setting

SW2
setting

1

2

1

2-5

± 1mA

ON

ON

OFF

OFF

0-20mA

OFF

ON

ON

ON

0-1mA

OFF

OFF

ON

OFF

4-20mA

ON

OFF

ON

ON

T a b l e 2 : 4 A O – O u t p u t C u r e n t s e t t i n g

4) Plug-in the module in the I/O slot and attach it to bracket using the two screws
5) Connect the 4AO cable and pass it through the device base window cables
6) Mount back the body shield
7) Mount back the plastic cover

The 4AO module is factory or Meter Shop plugged-in at the I/O slot