Measurement specifications – E-Mon E-PS-S-HV-RTU User Manual
Page 39

Appendix: Technical Specifications
33
Measurement Specifications
Accuracy
Parameter
Full Scale @
Input Range
%
Reading
% FS
Conditions
Range
Voltage V1-V3
(L-n)
277 x PT ratio
@ 277V
±0.05
±0.1
1% up to 120%
0 up to 999,000 V
Voltage V1-V3
(L-n)
120 x PT ratio @
120V
±0.05
±0.1
1% up to 140%
0 up to 999,000 V
Voltage V1-V3
(L-n)
69 x PT ratio
±0.05
±0.1
1% up to 140%
0 up to 999,000 V
Line current I1- I3
CT primary current ±0.06
±0.06 1% up to 200%In
0 up to 20,000 A
Line current I1- I3
CT primary current ±0.1
±0.06 200% up to 400%
0 up to 20,000 A
Line Fault current
I1- I3
CT primary current ±1.0
-
400%- 1000% In
0 up to 100,000 A
Active power
3xV FS×CT/1000
±0.2
±0.02 |PF| ≥ 0.5 *
-10,000,000 kW to
+10,000,000 kW
Reactive power
3xV FS×CT/1000
±0.3
±0.04 |PF| ≤ 0.9 *
-10,000,000 kvar to
+10,000,000 kvar
Apparent power
3xV FS×CT/1000
±0.2
±0.02 |PF| ≥ 0.5 *
0 to 10,000,000 kVA
Power factor
1.000
±0.2
|PF| ≥ 0.5, I ≥ 2% FSI
-0.999 to +1.000
50 Hz
-
±0.02 40-65 Hz
40.00 up to 64.99 Hz
Frequency
60 Hz
-
±0.02 45- 70 Hz
45.00 up to 69.99 Hz
Total Harmonic
Distortion, THD
V (I), %Vf (%If)
999.9
±1.5
±0.1
THD ≥ 1%,
V (I) ≥ 10% FSV (FSI)
0 to 999.9
Total Demand
Distortion, TDD, %
100
±1.5
TDD ≥ 1%,
I ≥ 10% FSI
0 to 100
Active energy
Import & Export
ANSI C12.20, Class 10/20, Acc. Class 0.2
0 to 999,999.999 MWh
Reactive energy
Import & Export
Class 0.5Sunder conditions as per IEC 62053-
23:2003
0 to 999,999.999 Mvarh
Apparent energy
Class 0.2 under conditions as per IEC 62053-
22:2003
0 to 999,999.999 MVAh
Symmetrical
components
Voltage FS
Current FS
Current FS
±1.0
±1.0
±3.0
10% - 120% FS
10% - 400% FS
200% - 1000%FS
Phasor angles
±1 degree
* @ 80% to 120% of voltage FS, 2% to 200% of current FS, and frequency 50/60 Hz
PT - external potential transformer ratio
CT - primary current rating of external current transformer
FSV - voltage full scale
FSI - current full scale
Vf - fundamental voltage
If - fundamental current
NOTES
1. Accuracy is expressed as ± (percentage of reading + percentage of full scale) ± 1 digit. This does not
include inaccuracies introduced by the user's potential and current transformers. Accuracy calculated at
1second average.
2. Specifications assume: voltage and current waveforms with THD ≤ 5% for kvar, kVA and PF, and
reference operating temperature 20°C - 26°C.
3. Measurement error is typically less than the maximum error indicated