Chapter 2 Installation

20

3) Plug-in the module in the COM slot and attach it to bracket using the two

screws

4) Connect the GSM/GPRS antenna cable expander and pass it through the

device base window cables

5) Mount back the body shield

6) Mount back the plastic cover

The GSM/GPRS module is factory or Meter Shop plugged-in at the COM slot

1) Apply power to the meter

2) After one minute the "LNK" GREEN
LED is flashing until it lights "ON"
continuously

3) The "RSSI" ORANGE LED will light
"ON" or blinks, the flashing rate is
proportional to the RF receive level
(RSSI), if RF receive level is high then
the led is "ON" continuously, if RF
receive level is poor then the led is
blinking

E T H E R N E T o r M O D E M o p t i o n a l m o d u l e

The Communication port – COM4 and IRIG-B interface input are provided by optional
modules: ETHERNET and MODEM.

To install the ETHERNET or MODEM module follow instructions:

1) Remove the plastic cover

2) Remove the body shield

3) Plug-in the module in the COM slot and attach it to bracket using the two

screws

4) Connect the ETH or MODEM cable and pass it through the device base window

cables

5) Mount back the body shield

6) Mount back the plastic cover

The ETHERNET or MODEM module is factory or Meter Shop plugged-in at the COM slot

F i g u r e 2 5 : E T H E R NE T m o d u l e