Appendix: Technical Specifications

27

Appendix: Technical Specifications

Inputs Ratings

AC Voltage
inputs

Va, Vb, Vc and Vref - 50/60Hz

High input
impedance = 10MΩ

Voltage rating:
120 up to 277 Volts (L-N), 207 to 480 Volts (L-L)

Voltage range
Crest factor >2 [V

L-N

x 1.2 x 2]

0 -332 V r.m.s,
peak up 665V (for PQ)

Maximum Line to Line voltage

1152 V r.m.s

Temporary over voltage between live conductors and
earth
Transient over voltage between live conductors and
earth (TRM optional module, from 15 µs up to ms)

1500 V r.m.s

6 kV peak, 2kV
measurement

Starting voltage

0.1%U

n

Burden per phase

< 0.5 VA

Overload withstand for 1 minute phase-to-ground
(ANSI C12.1 & IEC 62053-22, protective class II)

4000V r.m.s

Reference voltage
U

n

120V up to 277V

L-N (direct)
standard

Rated impulse voltage
(ANSI C12.1 & IEC 62052-11, protective class II)

6000V peak

Voltage rating:
57.73 up to 120 Volts (L-N), 100 to 207 Volts (L-L)

Voltage range
Crest factor >2 [V

L-N

x 1.2 x 2]

0 -144 V r.m.s,
peak up 288V (for PQ)

Maximum Line to Line voltage

500 V r.m.s

Temporary over voltage between live conductors and
earth
Transient over voltage between live conductors and
earth (TRM optional module, from 15 µs up to ms)

240 V r.m.s

1.5 kV peak

Starting voltage

1

0.1%U

n

Burden per phase

< 0.2 VA

Overload withstand for 1 minute phase-to-ground
(ANSI C12.1 & IEC 62053-22, protective class II)

4000V r.m.s

Reference voltage
U

n

57.73V up to

120V L-N (via PT)
optional

Rated impulse voltage
(ANSI C12.1 & IEC 62052-11, protective class II)

6000V peak

Voltage/Current
inputs

Terminals for wires size

Blades (Socket meter
standard – C12.10)

Ground input

Terminals for wires size

According to Socket meter
standard – C12.10

AC Current inputs 3 (4 optional) Galvanic isolated Inputs

Current class Imax

10A & 20A

Maximum measurable short circuit current (Isc)

10 x I

n

Burden per phase (In = 5 A)

< 0.2 VA

Starting current (I1, I2, I3) – average
Starting current (I1, I2, I3) – real time

0.2% I

n

1.0% I

n

Over current withstand for 1 s non-recurring

50 x I

n

Isolation

4000V r.m.s

Terminals for wires size

Blades (Socket meter
standard – C12.10)

Reference Current
Basic model In = 5
A
(TA = 2.5A)

3 (4 optional) Galvanic isolated Inputs

FORM 9 (39 optional)

1

Starting voltage, interruptions and dips measurement applicable only with installed APS