Appendix: Technical Specifications

30

Communication ports

COM1

Built-in Infra Red communication port

DISPLAY unit

RS232 communication, TTL level, max baud rate 19.2 kb/s

Protocols

MODBUS RTU/ASCII and DNP3.0

Optically isolated

2500V AC @ 1mn

IR port
Basic

Optical port per ANSI C12.18

Type 2

COM2

Plug-in modules isolated communication port

RS232 communication, TTL level, max baud rate 115.2 kb/s

Isolation

2500V AC @ 1mn

GSM/GPRS module

Quad Band GPRS class10

Antenna connection

Coax cable terminated with SMA
connector

Protocols

MODBUS/TCP or DNP3.0/TCP

MODEM module

Telephone Line according to FCCp.68
and TBR21

Line connection

RJ11

GSM/GPRS
MODEM
Optional module

1

Protocols

MODBUS/RTU, MODBUS/TCP or
DNP3.0, DNP3.0/TCP

COM3

Built-in serial communication port

RS-485 isolated

115.2 kb/s

Isolation

2500V AC @ 1mn

Protocols

MASTER/SLAVE MODBUS RTU/ASCII
and DNP3.0

basic

Terminals for wires size

2 x 2.5 mm

2

shielded twisted cable

Plug-in modules isolated communication port

Versatile RS-232/RS-485

Max. Baud rate

115.2 kb/s

Isolation

2500V AC @ 1mn

Protocols

MODBUS RTU/ASCII and DNP3.0

COM4
ETH-TX
MODEM
Optional module

1

Terminals for wires size

5 x 2.5 mm

2

shielded twisted cable

Plug-in modules network communication port

Wired LAN communication port with auto-
negotiation

IEEE 802.3

Ethernet port Baud rate

10/100 Mb/s

Protocols

MODBUS/TCP or DNP3.0/TCP
protocols and IEC 61850-8-1, up to
five non-intrusive simultaneous
connections, Telnet service port

ETH port Isolation

2500V AC @ 1mn

10/100Base-T
ETH-TX
Optional module

1

ETH connector

ETH cable terminated with Standard
RJ-45 connector

Communication port

Basic

USB communication port

Full speed Device

USB port Baud rate

12 Mb/s

USB – FS device
basic

Protocols

MODBUS RTU/ASCII and DNP3.0

1

Factory/Meter shop installable

Advertising