Console display unit, Real time clock, Environmental conditions – E-Mon E-PS-S-HV-RTU User Manual
Page 37: Construction, Standards compliance

Appendix: Technical Specifications
31
USB connector
Cable terminated with USB type A
Input Isolation
2500V AC @ 1mn
Time code signal
Demodulated (pulse-width coded)
Signal Level
Unbalanced 5V
Terminals for wires size
2 x 2.5 mm
2
twisted cable
Recommended cable
51Ohm low loss - RG58A/U (Belden
8219 or equivalent), TNC connector
IRIG-B
ETH-TX
MODEM
Optional module
1
Recommended GPS time code generator
Masterclock GPS-200A
Console Display Unit
Display Panel
LCD graphic bright display
Multiple screens display
Resolution
340 x 220 dots
Size
4'
Operational temperature
-20°C to + 70°C
Display
Backlit LCD display screen
Timeout operation
LEDs
Energy LED Pulsing
2 x RED (WATT & VAR)
Communication
IR port, COM1
ANSI C12.18
Accessible Buttons – SCROLL,
SELECT/ENTER
2
Sealed Button – DEMAND RESET
1
Navigator buttons
Under cover Button – TEST mode
1
Real Time Clock
5 ppm Accuracy @ 25°C
2.7 minute / year
RTC backup data retention
5 years
Log Memory
Non-volatile memory
(20years Data retention)
For energy and tariff registers logging,
EV-PQ-DATA-WV log
16 MB
Environmental Conditions
Operational temperature
-40 ºC to 75 ºC
Optional LCD Operational temperature
-20 ºC to 70 ºC
Storage temperature
-40 ºC to 85 ºC
Humidity
0 to 95% non-condensing
Construction
Socket Meter base enclosure
ANSI C12.10 for electronic meter
Size:
∅
6" x L 7" x base ∅ 7"
Weight
4 lb
Enclosure
With sealing cover
Mounting
ANSI C12.10 – FORM 9S/9A
Standards Compliance
EMC
ANSI C12.1
Reference: IEC 61000
1
Factory/Meter shop installable