Ransburg, Safety ground, Low voltage cable – Ransburg MicroPak Controller A11789 User Manual

Page 11

Advertising
background image

SAFETY GROUND

Install the ground wire assembly supplied with

the MicroPak Controller from the ground stud on

the rear of the controller to a true earth ground.

For maximum noise immunity, cut the ground

wire assembly to the shortest length required

and reinstall the end lug before making connec-

tions.

†

The ground wire assembly

MUST be con-

nected from the MicroPak Controller ground

stud to a true earth ground.

C A U T I O N

!

LOW VOLTAGE CABLE

Standard Low Voltage Cable

(A11791-XX)

Plug the connector of the low voltage cable as-

sembly into the appropriate receptacle on the

rear of the controller (see Figure 3). P1 is the out-

put for the leftmost MicroPak control unit, when

viewed from the front, and P2 is the output for

the rightmost MicroPak control unit, if installed.

When making the connection, line the red dot on

the connector with the red mark on the recepta-

cle and push in until it clicks. To remove, simply

pull back on the knurled portion of the connector.

Attach the low voltage cable(s) to the stress re-

lief bar using TR-SSEM-200 cable ties (supplied)

as shown in Figure 3.

Junction Box Cables

(A11498-XX and A11356-XX)

The spray gun can be ordered with special low

voltage cables (A11498-XX and A11356-XX)

for splicing to a junction box. This is sometimes

done in the field, to reduce the amount of cable

that has to be replaced if a failure of the cable

occurs. The control unit and gun ends of these

cables attach as described in the standard low

voltage cable section above. Follow the instruc-

tions below to wire the junction box ends of these

cables:

Junction Box in Hazardous Location

If the junction box is in the hazardous location,

an explosion-proof junction box must be used. In

this case, connect the numbered wires of cable

A11356-XX to the same numbered wire of cable

A11498-XX using a terminal strip inside the ex-

plosion-proof junction box. Ensure the junction

box is grounded to earth ground. Connect wire

18 (braid) of cable A11498-XX to the junction box

(ground). Seal the cable in the explosion-proof

junction box using appropriate explosion-proof

fittings and sealing compound. The exposed

area of the cable braids must be located on the

junction box side of the sealing compound.

Junction Box in Non-Hazardous

Location

If the junction box is in a non-hazardous location,

then it is not necessary to use an explosion-proof

junction box. In this case, use the supplied cable

gland (A11357-02) and gland nut (A11358-02) to

secure the cables at their entry and exit to the

junction box. Install the cable gland in the junc-

tion box and position the cable so that the spring

of the gland makes contact to the exposed braid

of the cable when the gland nut is tightened.

Ensure the junction box is grounded to earth

ground. Connect the numbered wires of cable

A11356-XX to the same numbered wire of cable

A11498-XX using a terminal strip inside the junc-

tion box. The braid of cable A11498-XX will be

grounded through its contact to the cable gland

spring and the grounded junction box. Wire 18,

therefore is unnecessary and may be trimmed

off. Connection in this manner will ensure maxi-

mum noise immunity.

MicroPak Controller - Installation

9