Ransburg, Description of table 1 interlock and i/o terminals, Current control – Ransburg MicroPak Controller A11789 User Manual

Page 14

Advertising
background image

DESCRIPTION OF TABLE

1 INTERLOCK AND I/O

TERMINALS

Input Terminals

kV Setpoint (0-10VDC)

0 to 10 VDC remote analog signal input that

controls applicator output from 0 to 100 kV DC

when high voltage is enabled. This input is active

when the MicroPak local/remote switch is in the

remote position. Otherwise control is from the

kV adjust knob on the front of the MicroPak. In

either mode, the kV setpoint can be viewed by

pushing and holding the View/Change Setpoint

switch (see Figure 8) on the front of the Micro-

Pak.

Voltage Control Over-Current

Setpoint (0-10VDC)

0 to 10VDC remote analog signal input that sets

the over-current point when high voltage is en-

abled. If the current goes above this setpoint an

overcurrent fault will occur. This input is active

when the MicroPak local/remote switch is in the

remote position and dipswitch SW3-1 on the

MicroPak process board (see Figure 6A) is set

to the ON position. The range of the over-cur-

rent setpoint in this mode is 0 to 10VDC. The

microamps are limited to 240 for voltage above

10VDC.

For example: 3.30VDC = 85 microamps

If the local/remote switch is in the remote position

and dipswitch SW3-1 is OFF, then potentiometer

R21 on the top of the MicroPak process board

Figure 5: Stripping of I/O Cable(s)

(see Figure 6A) will control the over-current set-

point. This mode is convenient if it is desired to

supply an analog input signal for the kV setpoint

but not for the over-current setpoint.

Finally, if the local/remote switch is in the local

position, the over-current setpoint is controlled

by the μA adjust knob on the front of the Micro-

Pak.

If any of the modes, the over-current setpoint

can be viewed by pushing and holding the View/

Change Setpoint switch (see Figure 8) on the

front of the MicroPak.

CURRENT CONTROL

Over-Current Setpoint (90-10VDC)

0 to 10VDC remote analog signal input that sets

the desired current. The current control unit will

limit the maximum current to this setpoint. If the

current goes over this setpoint, then a fault will

occur.

If the voltage setpoint is set low, then the unit

will only allow enough current to achieve the

kV setpoint. It may be simpler to think of the kV

setpoint as the controlling variable when the kV

setpoint is achieved before the current setpoint.

The range of current is 0 to 240 microamps with

0 to 10VDC analog input.

For example: 10VDC = 240 microamps

3.30VDC = 85 microamps

High Voltage Reset (24VDC)

24VDC remote input signal that allows remote

reset of fault conditions. When a fault occurs, a

momentary supply of 24VDC to this terminal will

reset the fault. Faults can also be reset by mov-

ing the kV ON/OFF toggle switch on the front of

the MicroPak to the OFF position and back to

the ON position. This input can also be used to

remove the MicroPak from ready mode.

High Voltage On (24VDC)

Remote input signal that enables high voltage.

When 24VDC is supplied to this terminal, high

voltage will be enabled. This input mode is active

in either local or remote mode when dipswitch

MicroPak Controller - Installation

12

Ransburg

CP-06-01.1

Advertising