Ransburg, Typical remote mode, Micropak controller - operation – Ransburg MicroPak Controller A11789 User Manual

Page 21

Advertising
background image

Figure 8: Operating Controls

Typical Remote Mode

1. Ensure the AC power, safety ground, low

voltage cable, I/O, and interlock connections

are made as described in the “Installation” sec-

tion of this manual.

2. Set the 0-10VDC kV setpoint input to its mini-

mum value (0 volts).

3. Turn the AC Power ON/OFF switch (see Fig-

ure 2) to the ON position. When the AC power

is on the green CPU Indicator on the front of the

discreet I/O module will illuminate.

4. Turn the MicroPak ON/OFF switch to the ON

position. The kV and μA displays will come on

along with the yellow MicroPak Power Indicator

located above the switch.

5. Supply a momentary ground connection to

the Ready input shown in Table 1. The yellow

High Voltage Ready Indicator should turn on.

6. Supply a 24VDC signal to the High Voltage

On input shown in Table 1. The red High Volt-

age On Indicator should turn on.

7. Adjust the 0-10VDC kV setpoint input to ob-

tain the desired value on the kV Meter. Ensure

the over-current setpoint is set above the maxi-

mum expected current, or an overload fault will

occur. The over-current setpoint can be adjust-

ed by changing the setpoint of R21 if dipswitch

SW3-1 is OFF, or by changing the value of the

0-10VDC over-current setpoint input (see Table

1) if dipswitch SW3-1 is ON.

8. To turn high voltage off, remove the 24VDC

signal from the high voltage on input.

9. When finished spraying, turn the AC Power

ON/OFF Switch (see Figure 2) to the OFF posi-

tion to prolong the life of the internal fan.

MicroPak Controller - Operation

19