Installation, Air & fluid connections, Air filter installation – Ransburg Aerobell Copes 75850 User Manual

Page 14

Advertising
background image

Aerobell Copes - Installation

INSTALLATION

AIR & FLUID CONNECTIONS

See Figure 6 for rear views of the Aerobell Copes

manifolds. Refer to this figure for proper location

of connections.

The Aerobell Copes shipping container includes the

basic atomizer assembly with bell and manifold.

Service tools required with the system are 2 (or more)

RPM-419 (wrenches) per bell spray zone or spray

station. (These service tools must be purchased

separately.) These are required to remove the bell

cup. Also required with the system is 1 (or more)

75852-

00 (retaining nut tool) per zone which are used

to remove the quick change Aerobell assembly.

Mount the Aerobell Copes securely to a stationary,

reciprocating or oscillating fixture using (Qty-4)

5/16-18 plastic (nonconductive) mounting screws.

AIR FILTER INSTALLATION

The following guidelines must be observed when

installing air filters for the Aerobell Copes system:

(See Figure 5 for additional information.)

1.

Use only recommended pre-filters and bearing

air filters as shown in Figure 5. Additional

system air filtration (i.e. refrigerated air dryer)

may also be used if desired.

2.

Use one bearing air filter per Aerobell

Copes.

3.

Mount the bearing air filter as close as possible

to the Aerobell Copes (do not mount further

than 30 ft. away).

4.

Where possible, the pre-filter(s) and bearing

air filter(s) should be mounted where they can

be easily seen so that operating personnel can

observe and determine when maintenance

is required.

5.

Standard black iron or galvanized piping may

be used prior to the HAF-503 or RPM-417

pre-filters only. All piping after the pre-filter

should be brass, stainless steel, aluminum, or

hose (poly, nylon, nyliner, etc.).

6.

Do not use tape, pipe dope, or other thread

sealant downstream of the bearing air filter.

Loose flakes of tape or other sealant can break

loose and plug the very fine air holes in the

turbine bearings.

7.

Use clear see-through air tubing between

the bearing air filter and bearing air

fitting to clearly indicate if oil or moisture

contamination is getting past the filter.

8.

If air heaters are used in the system

(to eliminate excessive in-line humidity

conditions) and the heated air will exceed

120

°F, the heaters must be located after

all filters to prevent damage to the filter

media.

10

LN-9230-00.1

>

Risk of arcing / fire hazard. The Aerobell

Copes must be located a safe distance from the

object to be sprayed, as well as all other grounded

objects. The safe distance is at least 1 inch per

10 kV of applied electrostatic voltage. Example:

If the Aerobell Copes is used with 70 kV applied

voltage, the electrode tips must be at least 7

inches from the object being sprayed.

W A R N I N G

W A R N I N G

!

>

Arcing / fire hazard exists if ungrounded

metal connections (air or fluid) are used in the

spray area. Use plastic nonconductive con-

nections, or ensure metal connections are at

ground potential.

W A R N I N G

!

Advertising