C. status menu, D. test mode – HTP 399M User Manual

Page 62

Advertising
background image

62


differential temperature setting of the boiler. The burner will not start until the outlet water temperature reaches a temperature equal to
the setting for the boiler, minus the differential EX: The boiler is set to heat at 180°F degrees and the differential is set at 30°F. The
burner will not start until the outlet temperature of the system reaches 149°F degrees (180°

– 30°F = 150°F). To adjust, press either

{S1}

(Decrease Value) or

{S2}

(Increase Value) Ranges 5°F to 30°F.


Press

{S3}

again and you will see the Indirect Setting de and an alternative value of 119 (with Vision Systems option). To adjust,

press either

{S1}

(Decrease Value) or

{S2}

(Increase Value).


The final adjustment in this mode is the Fahrenheit to Celsius measurement. Press

{S3}

again and you will see t and alternating value

of F. To change value, press

{S1}

or

{S2}

to choose the correct measurement.

C. STATUS MENU

Installers are also able to check the current status of boiler parameters by pressing

{S4}

for 3 seconds. Once activated, the display will

show

|d1|

alternating value of the actual outlet temperature. Actual values are displayed for each function. To view the next value, press

{S4}

. Listed below are the values which can be displayed. These values cannot be changed. To exit this menu, press

{S3}

to resume

normal operation.

Function

Value

d1

— Actual Temperature from outlet sensor

d2

— Actual Temperature from inlet sensor

d3

— If using a standard mechanical control, the control will display

|1|

for closed

|0|

for open. If the sensor is connected to the

SuperStor Indirect Fired Water Heater it will measure the actual temperature (Vision option).
d4

— Not used

d5

— Actual Temperature from the outdoor sensor (Vision option).

d6

— Actual Fan speed multiplied by 10 (Example: If fan speed displayed is

|410|

RPM x 10 = 4100 actual fan speed)

d7

— Actual Ionization current read from Flame Rectification probe

d8

— Actual Status of the Central Heating Circulator Off =

|0|

, On =

|1|

. (Vision option.)

d9

— Actual Status of the Indirect Fired Circulator Off =

|0|

, On =

|1|

. (Vision option.)

d10

— Actual Status bus communication

|co|

= connected,

|no|

= not connected

d11

— Central Heating Set Point

d12

— Power On Hours in units

d13

— Total Central Heat Hours

d14

— Total Indirect/dhw Hours

d15

— Passed Ignition Attempts

D. TEST MODE

This function is intended to simplify the gas valve adjustment if needed. Listed below are the recommended limits on each boiler and
the combustion settings. Automatic modulation does not take place when the controller is in Test mode, only temperature limitation
based on the boiler central heating set point. The user will be allowed to increase or decrease the fan speed by pressing in either

{S1}

or

{S2}

.


To activate Test mode, press

{S2}

and

{S3}

together for 1 second. Once activated, you will see

{Ser}

in the display and the fan speed

(shown in a multiple of 10). The measurement of the combustion levels should always be taken at the highest and lowest fan speed.
After 10 minutes, the Test mode stops automatically. To exit Test mode, press

{S1}

and

{S2}

together for 1 second.

COMBUSTION SETTINGS

HIGH FIRING RATES and LOW FIRING RATES ON ALL MODELS

NATURAL GAS

PROPANE LP

Low

High

Low

High

Carbon Monoxide (CO%)

0

– 20 ppm

70

– 135 ppm

0

– 20 ppm

80

– 150 ppm

Carbon Dioxide (CO

2

%)

8 ½% - 9 ½%

8 ½% - 9 ½%

9 ½% - 10 ½%

9 ½% - 10 ½%

Table 10

FAN SPEEDS

BOILER

HIGH

LOW

IGNITION

T50M

3000

1250

3000

T80M

4250

1200

3000

80M

3700

1600

3220

140M

3550

1400

2765

199M

4800

1500

2765

399M

7700

1900

3000

Table 11