HTP 399M User Manual

Page 67

Advertising
background image

67

Code

Description

Remedy

F02

Interrupted or shorted supply

(outlet) thermister.

1. Check the electrical connection to the thermister on the outlet manifold. Verify 5 VDC by checking in
Molex connector. Verify thermistor values by referencing the chart in this manual.
2. If connection is okay, replace thermister.

F03

Interrupted or shorted return

(inlet) thermister.

1. Check the electrical connection to the thermister on the outlet manifold. Verify 5 VDC by checking in
Molex connector. Verify thermistor values by referencing the chart in this manual.
2. If connection is okay, replace thermister.

F05

Supply (outlet) temperature

exceeds 230

o

F.

1. Check circulation pump operation.
2. Assure that there is adequate flow through the boiler by accessing the status menu and assuring that
there is less than a 50

o

F rise from the return thermister to the supply thermister.

F06

Return (inlet) temperature

exceeds 230

o

F.

1. Check circulation pump operation.
2. Assure that there is adequate flow through the boiler by accessing the status menu and assuring that
there is less than a 50

o

F rise from the return thermister to the supply thermister.

3. Check direction of flow on boiler circulator.

F09

No flame detected

– The boiler

will make three attempts at

ignition before the control goes

into this lockout condition. *See

spark electrode detail.

1. Watch the igniter through the observation window provided.
2. If there is no spark, check the spark electrode for the proper ¼” gap by holding two quarters together and
sliding them through the gap.
3. Remove any corrosion from the spark electrode and flame rectifier probe.
4. If there is a spark but no flame, check the gas supply to the boiler.
5. If there is a flame, check the flame sensor.
6. Check any flue blockage or condensate blocks.

F10

Loss of flame signal

– The

boiler will relight 4 times before

the control goes into this lockout

condition. Will reset in 1 hour.

1. Monitor the gas pressure to the unit while in operation.

2. Assure that the flame is stable when lit.
3. Check to see if the green light on the display module is out while the boiler is running.
4. If the green light doesn’t come on or goes off during operation check the flame signal on the status
menu.
5. If the signal reads less than 1 microampere, clean the flame rectifier probe.
6. If the flame rectifier probe continues to read low, replace it.
7. Check the stability of the flame rectification signal. If the signal is unstable, you may need to replace the
burner gasket.

F11F

False flame signal

– The boiler

will lock out if it senses a flame

signal when there should be

none present.

1. Turn the gas off to the unit at the service valve.
2. If the flame signal is still present replace the igniter.
3. If the flame signal is not present after turning off the gas supply, check the gas valve electrical
connection.
4. If there is no power to the gas valve, remove the valve and check for obstruction in the valve seat or
replace the gas valve.
5. Turn the gas on at the service valve after corrective action is taken.
6. Check for condensate back up. Condensate back up can damage the refractory wall. If the wall falls
against the rectifier probe, it may conduct the signal to ground, giving a false signal.

F13

Combustion fan speed low

The boiler will lock out if it

senses that the fan speed is

less than 70% of expected rate

for more than 60 seconds.

1. Check the combustion air fan wiring.
2. Check the quality of the 24 VAC signal by measuring from any connected safety to ground. A low voltage
situation may cause a “false” error code.
3. Replace the combustion air fan.
4. Replace the control board.

F14

Combustion fan speed high

The boiler will lock out if it

senses that the fan speed is

less than 130% of expected rate

for more than 60 seconds.

1. Check the combustion air fan wiring.
2. Replace the combustion air fan.
3. Replace the control board.

F18

Gas Valve Error

1. Make sure the connector is correctly connected to the gas valve.
2. Check the electrical wiring from the valve to the control board.
3. Voltage readings will be from 18-22 VDC on the outlet of the gas valve plug from any pin to ground. The
connector must remain in contact with the pins.
ON THE 399M only, check the 24 VAC relay block.
4. Replace the low voltage wiring harness assembly.
5. Replace control board.

F19

Supply voltage frequency out of range. (92-132 VAC 60 Hz)

F30

Watchdog

Call factory for further assistance.

F31

Parameter Memory

Call factory for further assistance.

F32

Parameter Memory Write Error

Call factory for further assistance.

F33

Programming Error

Call factory for further assistance.

PP

Parameters Programmed

Press

S4

to reset.

Nc

Internal processor error, due to incoming voltage problems. (92-132 VAC 60 Hz) May also occur if neutral wire is broken or damaged.

F

Internal Error

Table 16