64

DEFAULT

FUNCTION

FUNCTION

VALUE

DESCRIPTION

17

0

Interface Board Function

0 = Building Management, 1 = Enables Tekmar Modulating Control
(Consult with Tekmar to assure the Tekmar Control is compatible.)

18

1

Step Modulation – Regulates the burner output in 6 steps in one-minute intervals. This reduces short cycling.

1 = on, 0 = off

19

180

o

Indirect boiler set point (flow)

Temperature default = 119

o

to 180

o

20

1

Not applicable

NOTE: The maximum water temperature leaving the boiler is limited to 185

o

F.

Table 12 - *Central Heating Curve Function

Central heating demand is detected when the room thermostat closes. When an
outside sensor is also connected, the supply temperature will depend on the factory
default central heating curve.

To set your heat curve, you will have to set the following parameters:

1. Minimum outside design temperature: Function 8.

2. Design supply water temperature at the minimum design outside temperature:
Function 9.

3. Maximum outside design temperature: Function 10.

4. Design supply water temperature at the maximum outside temperature: Function
11
.

NOTE: The homeowner can adjust the heat curve down by adjusting the central
heating temperature to a lower setting.















CONTROL PROGRAM REFERENCE CHART

FUNCTION

DEFAULT

SETTING

PROGRAMMED

SETTING

1

de

No change allowed

2

149

o

F

No change allowed

3

160

o

F

4

36

o

F

No change allowed

5

7

o

F

6

0 Min.

7

68

o

F

8

5

o

F

9

180

o

F

10

68

o

F

11

95

o

F

12

68

o

F

13

0 Min.

14

30 Min.

15

0

16

0

17

0

18

1

19

180

o

F

Table 13

– Reference Chart