IAI America PCON-CFA User Manual

Page 62

Advertising
background image

2. ACON-C/CG,

PCON-C/CG


56

(12) Zone 1 (ZONE1)

[PLC input signal]

Zone 2 (ZONE2)

[PLC input signal]

Position zone (PZONE) [PLC input signal]

Each signal turns ON when the current position of the actuator is inside the specified zone, and turns OFF when
the current position is outside the zone.
[1] Zone

1,

zone

2

Each zone is set by user parameters.
The ZONE1 signal is set by parameter No. 1, “Zone boundary 1+” and No. 2, “Zone boundary 1-.”
The ZONE2 signal is set by parameter No. 23, “Zone boundary 2+” and No. 24, “Zone boundary 2-.”
The ZONE1 and ZONE2 signals become effective following a completion of home return, after which they will
remain effective even while the servo is turned off.
[2] Position

zone

Each zone is set in the position table or using the zone boundary channels.
In the position/simple direct mode, the PZONE signal is set in the position table.
In the full direct mode, the PZONE signal is set using the zone boundary channels.
(*) The PZONE signal is not available in the half direct mode.
The PZONE signal becomes effective when a move command is issued following a completion of home return,
after which it will remain effective even while the servo is turned off.













Zone signal

Actuator operation

+ direction

Home

Zone setting-

Zone setting+

Advertising
This manual is related to the following products: