IAI America RCM-GW-DV User Manual

Page 64

Advertising
background image

58

DeviceNet Gateway


With each function, the top row indicates positioner operation, while the bottom row indicates simple direct
operation.

Key function

: Direct control

Δ: Indirect

control

X: Disabled

Remarks

Home return operation

Δ

Positioning operation is performed by specifying an
applicable number in the position table. *1

Positioning operation

Δ

Set all positioning data other than position data
in the position table, and specify the position
data and position table number at the same
time.

Δ

Set in the position table. *1

Speed/acceleration setting

Δ

Set in the position table.

Δ

Set in the position table. *1

Pitch (incremental) feed

X

Pitch feed data cannot be processed directly.
The host PLC must issue each command by
adding/subtracting the pitch-feed distance data
to/from the current position.

Δ

Set in the position table. *1

Push-motion operation

Δ

Set in the position table.

Δ

Speed change during movement

Δ

Speed change is implemented by combining
two or more position numbers. (Refer to the
operation manual for your controller.)

Δ

Set in the position table. *1

Operation with acceleration and
deceleration set differently

Δ

Set in the position table.

Pause

The zone signal output is set in the position
table or via a parameter. *2

Zone signal output

X

The current position data is constantly output
from the Gateway, so use the PLC to monitor
the current position data. *3

*4

PIO pattern selection

X *5


*1 The position table data can be written (rewritten) from the PLC using a request command (position

table data write). To use this function, the necessary data must be written to the position data
beforehand.

*2 The current position data can be read using a request command, but this data is not output constantly.
*3 No strobe signal is provided for the current position data. To check the current position from the PLC

during movement, set zones and check if the data has remained inside a given zone for at least two
scans.

*4 This parameter (No. 25) is not available with PCON-SE, ACON-SE and ERC2-SE controllers.
*5 Set the PIO pattern selection parameter (No. 25) of each connected controller to “0” (standard type).