Introduction

This chapter describes

specifications of the

MicroSmart

AS-Interface master module and applicable cables.

AS-Interface Master Module Type Number

The AS-Interface master module can connect a maximum of 62 digital I/O slaves. A maximum of seven analog I/O slaves
can also be connected to the AS-Interface master module (compliant with AS-Interface ver. 2.1 and analog slave profile
7.3).

The AS-Interface master module can be used with the 20-I/O relay output slim type CPU modules (FC4A-D20RK1 and
FC4A-D20RS1) and the 40-I/O slim type CPU modules (FC4A-D40K3 and FC4A-D40S3). Use a CPU module version of
201 or higher. When using

WindLDR

, use ver. 4.21 or higher.

Module Name

Type No.

AS-Interface Master Module

FC4A-AS62M

Caution

• The AS-Interface master module cannot be used with the all-in-one type CPU modules and the

20-I/O transistor output slim type CPU modules.

• Only one AS-Interface master module can be connected to the slim type CPU module. If more

than one AS-Interface master module is connected, an error occurs and special data register
D8037 (quantity of expansion I/O modules) stores error code 40 (hex).

• Normally, a maximum of seven expansion I/O modules can be connected to the slim type CPU

module. But when the AS-Interface master module is connected, only a total of six expansion
modules can be connected, including the AS-Interface master module. Do not connect more than
six expansion modules due to the amount of heat generated. If more than six expansion modules,
including the AS-Interface master module, are connected, an error occurs and special data regis-
ter D8037 (quantity of expansion I/O modules) stores error code 20 (hex).

• The AS-Interface master module can connect a maximum of seven analog I/O slaves. When more

than seven analog I/O slaves are connected, the AS-Interface system will not operate correctly.