IDEC MicroSmart AS-i User Manual

Page 35

Advertising
background image

6: AS-I

NTERFACE

O

PERANDS

6-4

M

ICRO

S

MART

AS-I

NTERFACE

M

ASTER

M

ODULE

U

SER

S

M

ANUAL

Analog I/O Data of Analog Slaves

The I/O data for a maximum of seven analog slaves (four channels for each slave) on the AS-Interface bus is stored to AS-
Interface data registers in the CPU module. The analog slave addresses (1 to 31) are in the ascending order. The input data
for each analog slave is allocated to data registers D1700 to D1731, and the output data is allocated to D1732 to D1763.

The AS-Interface master module is compliant with analog slave profile 7.3.

Analog Input Data

Analog Input

Channel No.

Data Format

D1700

Bytes 0 and 1

Channel 1

1st data

(AI0)

D1701

Bytes 2 and 3

Channel 2

D1702

Bytes 4 and 5

Channel 3

D1703

Bytes 6 and 7

Channel 4

D1704

Bytes 8 and 9

Channel 1

2nd data

(AI1)

D1705

Bytes 10 and 11

Channel 2

D1706

Bytes 12 and 13

Channel 3

D1707

Bytes 14 and 15

Channel 4

D1708

Bytes 16 and 17

Channel 1

3rd data

(AI2)

D1709

Bytes 18 and 19

Channel 2

D1710

Bytes 20 and 21

Channel 3

D1711

Bytes 22 and 23

Channel 4

D1712

Bytes 24 and 25

Channel 1

4th data

(AI3)

D1713

Bytes 26 and 27

Channel 2

D1714

Bytes 28 and 29

Channel 3

D1715

Bytes 30 and 31

Channel 4

D1716

Bytes 32 and 33

Channel 1

5th data

(AI4)

D1717

Bytes 34 and 35

Channel 2

D1718

Bytes 36 and 37

Channel 3

D1719

Bytes 38 and 39

Channel 4

D1720

Bytes 40 and 41

Channel 1

6th data

(AI5)

D1721

Bytes 42 and 43

Channel 2

D1722

Bytes 44 and 45

Channel 3

D1723

Bytes 46 and 47

Channel 4

D1724

Bytes 48 and 49

Channel 1

7th data

(AI6)

D1725

Bytes 50 and 51

Channel 2

D1726

Bytes 52 and 53

Channel 3

D1727

Bytes 54 and 55

Channel 4

D1728

Bytes 56 and 57

(reser ved)

D1729

Bytes 58 and 59

D1730

Bytes 60 and 61

D1731

Bytes 62 and 63

Caution

• The maximum number of analog slaves that can be connected to the AS-Interface bus is seven. Do

not connect eight or more analog slaves to one bus, otherwise the slaves will not function correctly.

• When data registers D1700 through D1731 allocated to analog inputs contain 7FFF, do not use this

data for programming, because this value is reserved for a special meaning as follows:

Unused channel on a slave allocated to analog slave. (For a channel on a slave not allocated an
analog slave, the corresponding data register holds an indefinite value.)
Data over flow.
Communication between the master and analog slave is out of synchronism.

• When using analog slaves, read the user’s manual for the analog slave to process the data properly.

Advertising