Installation and wiring, Installation location, Nstallation – IDEC MicroSmart AS-i User Manual

Page 14: Iring

Advertising
background image

M

ICRO

S

MART

AS-I

NTERFACE

M

ASTER

M

ODULE

U

SER

S

M

ANUAL

3-1

3: I

NSTALLATION

AND

W

IRING

Introduction

This chapter describes the methods and precautions for installing and wiring the AS-Interface master module.

Before starting installation and wiring, be sure to read “Safety Precautions” in the beginning of this manual and under-
stand precautions described under Warning and Caution.

Installation Location

The

MicroSmart

modules must be installed correctly for optimum

performance.

The

MicroSmart

is designed for installation in a cabinet. Do not

install the

MicroSmart

outside a cabinet.

The environment for using the

MicroSmart

is “Pollution degree 2.”

Use the

MicroSmart

in environments of pollution degree 2 (accord-

ing to IEC 60664-1).

Make sure that the operating temperature does not drop below 0°C
or exceed 55°C. If the temperature does exceed 55°C, use a fan or
cooler.

Mount the

MicroSmart

on a vertical plane as shown at right.

To eliminate excessive temperature build-up, provide ample venti-
lation. Do not install the

MicroSmart

near, and especially above,

any device which generates considerable heat, such as a heater,
transformer, or large-capacity resistor. The relative humidity should
be above 30% and below 95%.

The

MicroSmart

should not be exposed to excessive dust, dirt, salt,

direct sunlight, vibrations, or shocks. Do not use the

MicroSmart

in

an area where corrosive chemicals or flammable gases are present.
The modules should not be exposed to chemical, oil, or water
splashes.

• Turn off the power to the AS-Interface master module before starting installation, removal, wir-

ing, maintenance, and inspection of the AS-Interface master module. Failure to turn power off
may cause electrical shocks or fire hazard.

• Emergency stop and interlocking circuits must be configured outside the

MicroSmart

. If such a

circuit is configured inside the

MicroSmart

, failure of the

MicroSmart

may cause disorder of the

control system, damage, or accidents.

• Special expertise is required to install, wire, program, and operate the

MicroSmart

. People with-

out such expertise must not use the

MicroSmart

.

Warning

Caution

• Prevent metal fragments and pieces of wire from dropping inside the

MicroSmart

housing. Put a

cover on the

MicroSmart

modules during installation and wiring. Ingress of such fragments and

chips may cause fire hazard, damage, or malfunction.

• Do not touch the connector pins with hand, otherwise electrostatic discharge may damage the

internal elements.

Mounting Clip
BNL6P

Advertising