AS-Interface Cable Wiring

Before wiring the AS-Interface cable, remove the AS-Interface cable terminal block from the AS-Interface cable connector
on the AS-Interface master module.

AS-Interface specifies use of brown cables for the AS-Interface + line, and blue cables for the AS-Interface – line. Connect
the cables to match the color labels on the terminal block. Tighten the terminal screws to a torque of 0.5 to 0.6 N·m.

Insert the terminal block to the connector on the AS-Interface master module, and tighten the mounting screws to a torque
of 0.3 to 0.5 N·m.

Power Supply

Power Supply Wiring Diagram

A recommended power supply wiring diagram is shown below. Use a common power switch for both the CPU module
power supply and AS-Interface power supply to make sure that both power supplies are turned on and off at the same time.

Note: A failed slave can be replaced with a new slave with address 0 without turning off the power to the CPU module and
the AS-Inter face line. But, if power has been turned off before replacing the slaves, install a new slave with address 0 and
take one of the following steps, because the AS-Inter face master module has to be initialized to enable communication.

Disconnect the AS-Inter face cable connector and turn on both power supplies. Five seconds later, connect the AS-Inter face
cable connector.

Turn on the CPU module power supply first. Five seconds later, turn on the AS-Inter face power supply.

Blue AS-Inter face –

Use a ferrule.

Brown AS-Inter face +

Use a ferrule.

Blue Label

Brown Label

Caution

• When turning off the power to the CPU module, also turn off the AS-Interface power supply. If

the CPU module is powered down and up while the AS-Interface power remains on, AS-Interface
communication may stop due to a configuration error, resulting in a communication error.

• Turn on the AS-Interface power supply no later than the CPU module power supply, except when

slave address 0 exists on the network. The two power supplies may be turned off in any order.

AS-Interface Power Supply

30V DC

Slim Type CPU Module

FC4A-D40K3

AS-Inter face Master Module
FC4A-AS62M

Slave 1

Slave 2

AC Power

CPU Module Power Supply

24V DC

Power Switch

AS-Inter face Power Switch (Note)

AS-Inter face Cable Connector

VLSV (ver y low safety voltage)