5: P

USHBUTTONS

AND

LED I

NDICATORS

5-4

M

ICRO

S

MART

AS-I

NTERFACE

M

ASTER

M

ODULE

U

SER

S

M

ANUAL

Status LEDs

The operation modes of the AS-Interface master module can be changed by pressing the pushbuttons on the front of the
AS-Interface master module or by executing ASI commands. The operation modes can be confirmed on the six status
LEDs on the AS-Interface master module. For details about the ASI commands, see page 6-17.

Status LED Indication

*1: Goes off when AS-Inter face power is not supplied.
*2: Goes on when an error is found on the AS-Inter face bus.

Address LEDs and I/O LEDs

The operating status and I/O status of each slave can be monitored on the address LEDs and I/O LEDs on the front of the
AS-Interface master module.

Slave Operating Status

The operating status of each slave can be determined by viewing the address LEDs and I/O LEDs.

Slave I/O Status

The I/O status of each slave can be monitored on the address LEDs and I/O LEDs. Use the short press to change the slave
address when monitoring slave I/O status on the AS-Interface master module. A short press on PB1 increments the
address. At the last address (31B), another short press will return to the first address (0A). A short press on PB2 decre-
ments the address. At the first address (0A), another short press will return to the last address (31B).

The figures below illustrate what happens when you press the PB1 button while the address LEDs indicate 25A. The
address LEDs increment to 26A where a slave is assigned. Note that the address LEDs flash if no slave is assigned.

Status LED

PWR

FLT

LMO

CMO

OFF

CNF

Connected Mode

Normal Protected Mode

ON

*1

OFF

*2

OFF

ON

OFF

OFF

Normal Protected Offline

ON

*1

ON

OFF

ON

ON

OFF

Normal Protected
Data Exchange Off

ON

*1

ON

OFF

ON

OFF

OFF

Local Mode

Protected Mode

ON

*1

OFF

*2

ON

OFF

OFF

OFF

Configuration Mode

ON

*1

OFF

*2

ON

OFF

OFF

Flash

Address LED

I/O LED

Description

ON

ON or OFF

The slave at this address is active.

ON

Flash

The slave at this address is active, but has an error.

Flash

OFF

This address is not assigned a slave.

OFF

OFF

The AS-Inter face bus communication is disabled because the AS-Inter face power
is not supplied or the AS-Inter face master module is in normal protected offline.

Monitoring Slave Address 25A
Address LEDs are flashing since
no slave is assigned.

Shor t press

on PB1

I/O LEDs

indicate statuses

Monitoring Slave Address 26A
Address LEDs go on and I/O
LEDs indicate the statuses.