CT-8000 S3 USER’S MANUAL
REV 1
53
Select the resistance value by pressing the corresponding key (
[1]
,
[2]
, or
[3]
).
Continue to step d.
d. The following screen will be displayed:
Press the
[1]
key (WINDOW = 1 SEC).
NOTE
The 1-second timing window is used for breaker timing. The 10 and 20-
second timing windows are used for long timing events such as for timing
circuit-switchers.
e. The following screen will be displayed:
Press the
[1]
key (INTERNAL TRIGGER).
f. The following screen will be displayed:
Press the
[1]
key (OPEN).
TIMING MODE:
1.
OPEN 2. CLOSE
3. O-C 4. C-O
5. O-C-O
TRIGGER MODE:
1.
INTERNAL TRIGGER
2.
EXTERNAL TRIGGER
TIMING WINDOW:
1.
WINDOW = 1 sec
2.
WINDOW = 10 SEC
3.
WINDOW = 20 SEC
resistor value:
1.
LESS THAN 1000 OHMS
2.
1000 to 2000 OHMS
3.
MORE THAN 2000 OHMS