CT-8000 S3 USER’S MANUAL
REV 1
71
Press the
[2]
key (YES) if you are timing a circuit breaker with insertion resistors.
The following screen will be displayed:
Select the resistance value by pressing the corresponding key (
[1]
,
[2]
, or
[3]
).
Continue to step d.
d. The following screen will be displayed:
Press the
[1]
key (INTERNAL TRIGGER).
e. The following screen will be displayed:
Press the
[1]
key (OPEN).
f. The following screen will be displayed:
Hold down the
[ARM]
switch and press the
[START]
key.
HOLD "ARM" UNTIL
TEsT COMPLETES.
"START" TO BEGIN
"STOP" TO ABORT
TIMING MODE:
1.
OPEN 2. CLOSE
3. O-C 4. C-O
5. O-C-O
TRIGGER MODE:
1.
INTERNAL TRIGGER
2.
EXTERNAL TRIGGER
resistor value:
1.
LESS THAN 1000 OHMS
2.
1000 to 2000 OHMS
3.
MORE THAN 2000 OHMS