44 avi recommended exhaust flow rates – XLT XD-9004E User Manual

Page 44

Advertising
background image

Technical Support US: 888-443-2751

Technical Support INTL: 316-943-2751

44

AVI RECOMMENDED EXHAUST FLOW RATES

In accordance with mechanical codes, make up air must be supplied. For commercial

kitchen make up air, the amount is determined by the exhaust hood flow rate requirements & all
other exhaust flow rate requirements in the kitchen.

At a minimum, smoke candles must be used for a Capture & Containment (C&C) test. Re-

fer to the Ventilation Requirements disclosed in the Oven section in this manual.

A Test & Balance (TAB) report is recommended after installation has been completed.

Below are the minimum items to be included is this report:

Total airflow on all A/C, Make-Up Air (MUA), & exhaust systems.

Airflow on each supply & exhaust grille.

Airflows on exhaust hoods compared to design specifications.

A final air balance report, with any corrections of issues found in the report, will help to

insure that your building systems are functioning properly & efficiently.

Refer to “Oven Ventilation Requirements & Guidelines”

Top Middle Bottom

500

500

500

500

[14.16]

[14.16]

[14.16]

[14.16]

500

500

500

500

[14.16]

[14.16]

[14.16]

[14.16]

506

644

828

966

[14.33]

[18.24]

[23.45]

[27.35]

506

644

828

966

[14.33]

[18.24]

[23.45]

[27.35]

500

500

500

500

[14.16]

[14.16]

[14.16]

[14.16]

506

644

828

966

[14.33]

[18.24]

[23.45]

[27.35]

766

975

1254

1463

[21.69]

[27.61]

[35.51]

[41.43]

506

644

828

966

[14.33]

[18.24]

[23.45]

[27.35]

766

975

1254

1463

[21.69]

[27.61]

[35.51]

[41.43]

766

975

1254

1463

[21.69]

[27.61]

[35.51]

[41.43]

766

975

1254

1463

[21.69]

[27.61]

[35.51]

[41.43]

Exhaust Flow Rates VOLUME (min. recommended)

Switches On

18xx

32xx

38xx

24xx

Double

Triple

X

Single

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

NOTE

All values are CFM [M3/Min] unless otherwise noted. Figures represent TOTAL
VOLUME measured at the duct.

Advertising