AVI HOOD ELECTRICAL REQUIREMENTS

Inputs into Junction Box

The AVI Hood system provides:

 Three (3) switching outputs for HVAC dampers and dedicated units
 One (1) 230 VAC, 10 Amp, variable frequency, three phase power output for the ventilation

exhaust fan.

 Up to Three (3) receptacles for ovens.

 One (1) 120 VAC fire alarm signal for Standard hoods, or one (1) 24 VAC fire alarm signal for

World Hoods

Outputs from Junction Box

# of Circuits

Rating

Purpose

1

208/240 VAC, 1 Phase, 60 Hz, 6 Amp

VFD Controller

up to 3

120 VAC, 1 Phase, 60 Hz, 20 Amp

Ovens

1

120 VAC, 1 Phase, 60 Hz, 1 Amp

System Power

1

230 VAC, 1 Phase, 50 Hz, 6 Amp

VFD Controller

up to 3

230 VAC, 1 Phase, 50 Hz, 10 Amp

Ovens

1

230 VAC, 1 Phase, 50 Hz, 1 Amp

System Power

Standard

World

AVI Hood Electric Utility Specifications