Installation

(for qualified installers only)

Travis Industries

9 3 5 0 8 1 1 5

4 0 5 0 1 1 3

Approved Venting Configurations with a Horizontal Termination
and One 90° Elbow

•

If using a Snorkel Termination (14” or 36”) add the snorkel height to the vertical height (snorkel
terminations are used primarily for basement installations).

•

The termination must fall within the shaded area shown in the chart. Use the indicated restrictor
position.

5 feet

10 feet

15 feet

19' (max)

0 feet

5 feet

0 feet

0 feet

5 feet

10 feet

15 feet

Restrictor Position # 5

NOTE:

Restrictor positions are based

upon lab tests. The ideal

restrictor position may vary

slightly, especially when the

termination is near a

demarkation line.

Restrictor

Position # 1

10 feet

15 feet

20 feet

24 ' (max)

0 feet

5 feet

10 feet

15 feet

20 feet

24 ' (max)

19' (max)

NOTE:
Horizontal sections require a 1/4"
rise every 12" of travel.

NATURAL GAS: Min. 2' Section Required

PROPANE (LP): Min. 3' Section Required