Installation

CAS User’s Guide 25

The next table shows the location of RC and RD on the analog input
board. (The analog input board is the upper board of the two-board set.)

A wire trace on the printed circuit board jumpers the RC position. When
you place a resistor in the RC position, cut the wire trace that connects
the two resistor terminals.

Scaling and Calibration

The CAS provides offset calibration for thermocouples and other fixed
ranges, and offset and span (gain) calibration for linear and pulse inputs.
(Offset and span calibration convert linear analog inputs into
engineering units using the Mx+B function.)

In order to scale linear input signals, you must:

1.

Install appropriate scaling resistors.

2.

Select the display format. The smallest possible range is
-.9999 to +3.0000; the largest possible range is -9999 to 30000.

3.

Enter the appropriate scaling values for your process.

For more information about input scaling and input offset, see Setup
Channel Inputs in Chapter 4: Setup.

Channel #

RC

RD

1

R58

R42

2

R56

R40

3

R54

R38

4

R52

R36

5

R50

R34

6

R48

R32

7

R46

R30

8

R44

R28

9

R57

R41

10

R55

R39

11

R53

R37

12

R51

R35

13

R49

R33

14

R47

R31

15

R45

R29

16

R43

R27