Watlow EZ-ZONE RUI/Gateway User Manual

Page 15

Advertising
background image

Watlow EZ-ZONE

®

RUI/Gateway

12

Chapter 3 Keys and Displays

Changing the Position of a Controllers Op-

erations Page and or Profiling Page in the

Lockout Menu

To change the position of the Operations Page or Pro-

filing Page in the Lockout Menu, you must go to the

Lock Operations Page parameter [LoC;O] or Lock Pro-

filing Page parameter [LoC;P] in the Lockout Menu in

the Factory Page.

• To go to the Factory Page from the Home Page,

press both the Advance

and Infinity ˆ keys

for six seconds. [CUSt] will appear in the Upper

Display and [FCty] will appear in the Lower

Display.

• Press the Up ¿ or Down ¯ key to move to the

Lockout Menu [`LoC].

• Press the Advance Key

to select a parameter.

• Press the Up ¿ or Down ¯ key to change the

parameter value. The value you select (1, 2 or

3) will determine the position of the Operations

Page or Profiling Pages in the Lockout Menu in

the RUI Page.

• Press the Infinity Key ˆ to move backwards

through the levels: parameter to menu; menu to

Home Page.

• Press and hold the Infinity Key ˆ for two seconds

to return to the Home Page.

Note:

[rLoC]

and [SLoC] settings of the RUI will always

take precedence over any other individual controller

settings. In other words, if an RUI is on a network

with multiple PM controllers where all of the PM

controllers have [SLoC] set to 0 (not writable) and

the RUI has [SLoC] set to 5, all writable param-

eters in all PM controllers can be written to via the

RUI. Conversely, if all PM controllers have [SLoC]

set to 5 and the RUI has it set to 0 all of the PM

controllers will be write protected. If it is required

that protection for any given controller not be over-

ridden by the RUI turn to the Features section of

the controller user manual and find the section en-

titled "Using Password Security".

Example 1

The operator wants to read all the menus and not al-

low any parameters to be changed.
In the RUI Page, Lockout Menu, set Read Lock
[rLoC]

to 5 and Set Lock [SLoC] to 0.

Example 2

The operator wants to read and write to the Home

Page and Profiling Page, and lock all other pages and

menus.
In the RUI Page, Lockout Menu, set Read Lock
[rLoC]

to 2 and Set Lock [SLoC] to 2.

In the Factory Page, Lockout Menu, set Lock Op-

erations Page [LoC;O] to 3 and Lock Profiling Page
[LoC;P]

to 2.

Example 3

The operator wants to read the Operations Page,

Setup Page. Profiling Page, Diagnostics Menu, Lock

Menu, Calibration Menu and Custom Menus. The op-

erator also wants to read and write to the Home Page.
In the RUI Page, Lockout Menu, set Read Lock
[rLoC]

to 1 and Set Lock [SLoC] to 5.

In the Factory Page, Lockout Menu, set Lock Op-

erations Page [LoC;O] to 2 and Lock Profiling Page
[LoC;P]

to 3.

Advertising