RMC CIP T to O Implicit Assemblies

Assembly

Members

Assembly

Class, Instance,

Attritbute

RM Module

Data Type

Parameter

Parameter

Class, Instance,

Attritbute

PLC

Data Type

0

Cannot be changed

Binary

Device Status

none

DINT

1

0x77, 0x02, 0x01

DINT

Analog Input 1, Analog Input Value (filtered)

0x68, 0x01, 0x01

REAL

2

0x77, 0x02, 0x02

DINT

Analog Input 1, Input Error

0x68, 0x01, 0x02

DINT

3

0x77, 0x02, 0x03

DINT

Analog Input 2, Analog Input Value (filtered)

0x68, 0x02, 0x01

REAL

4

0x77, 0x02, 0x04

DINT

Analog Input 2, Input Error

0x68, 0x02, 0x02

DINT

5

0x77, 0x02, 0x05

DINT

Analog Input 3, Analog Input Value (filtered)

0x68, 0x03, 0x01

REAL

6

0x77, 0x02, 0x06

DINT

Analog Input 3, Input Error

0x68, 0x03, 0x02

DINT

7

0x77, 0x02, 0x07

DINT

Analog Input 4, Analog Input Value (filtered)

0x68, 0x04, 0x01

REAL

8

0x77, 0x02, 0x08

DINT

Analog Input 4, Input Error

0x68, 0x04, 0x02

DINT

9

0x77, 0x02, 0x09

DINT

Alarm 1, Alarm State

0x6D, 0x01, 0x09

DINT

10

0x77, 0x02, 0x0A

DINT

Alarm 2, Alarm State

0x6D, 0x02, 0x09

DINT

11

0x77, 0x02, 0x0B

DINT

Alarm 3, Alarm State

0x6D, 0x03, 0x09

DINT

12

0x77, 0x02, 0x0C

DINT

Alarm 4, Alarm State

0x6D, 0x04, 0x09

DINT

13

0x77, 0x02, 0x0D

DINT

Alarm 5, Alarm State

0x6D, 0x05, 0x09

DINT

14

0x77, 0x02, 0x0E

DINT

Alarm 6, Alarm State

0x6D, 0x06, 0x09

DINT

15

0x77, 0x02, 0x0F

DINT

Alarm 7, Alarm State

0x6D, 0x07, 0x09

DINT

16

0x77, 0x02, 0x10

DINT

Alarm 8, Alarm State

0x6D, 0x08, 0x09

DINT

17

0x77, 0x02, 0x11

DINT

Control Loop 1, Output Power

0x97, 0x01, 0x0F

REAL

18

0x77, 0x02, 0x12

DINT

Control Loop 2, Output Power

0x97, 0x02, 0x0F

REAL

19

0x77, 0x02, 0x13

DINT

Control Loop 3, Output Power

0x97, 0x03, 0x0F

REAL

20

0x77, 0x02, 0x14

DINT

Control Loop 4, Output Power

0x97, 0x04, 0x0F

REAL

21

0x77, 0x02, 0x15

DINT

None Specified

- - - -

- - - -

22

0x77, 0x02, 0x16

DINT

None Specified

- - - -

- - - -

23

0x77, 0x02, 0x17

DINT

None Specified

- - - -

- - - -

24

0x77, 0x02, 0x18

DINT

None Specified

- - - -

- - - -

25

0x77, 0x02, 0x19

DINT

None Specified

- - - -

- - - -

26

0x77, 0x02, 0x1A

DINT

None Specified

- - - -

- - - -

27

0x77, 0x02, 0x1B

DINT

None Specified

- - - -

- - - -

28

0x77, 0x02, 0x1C

DINT

None Specified

- - - -

- - - -

29

0x77, 0x02, 0x1D

DINT

None Specified

- - - -

- - - -

30

0x77, 0x02, 0x1E

DINT

None Specified

- - - -

- - - -

31

0x77, 0x02, 0x1F

DINT

None Specified

- - - -

- - - -

32

0x77, 0x02, 0x20

DINT

None Specified

- - - -

- - - -

33

0x77, 0x02, 0x21

DINT

None Specified

- - - -

- - - -

34

0x77, 0x02, 0x22

DINT

None Specified

- - - -

- - - -

35

0x77, 0x02, 0x23

DINT

None Specified

- - - -

- - - -

36

0x77, 0x02, 0x24

DINT

None Specified

- - - -

- - - -

37

0x77, 0x02, 0x25

DINT

None Specified

- - - -

- - - -

38

0x77, 0x02, 0x26

DINT

None Specified

- - - -

- - - -

39

0x77, 0x02, 0x27

DINT

None Specified

- - - -

- - - -

40

0x77, 0x02, 0x28

DINT

None Specified

- - - -

- - - -

CIP Implicit Assembly

Target (

RMC

) to Originator (Master)

Note:

When configuring the gateway T to O assembly size for the RMC, the maximum size is using the RUI is 20.

The graphic above shows 41 members where the first member (0 - Device Status) is implied. When configur-

ing the Master assembly size, Device Status cannot be omitted.

Advertising