Watlow EZ-ZONE
®
RUI/Gateway
•
6
•
Chapter 2 Install and Wire
Power
Power
power
power
98
99
CF
CD
CE
B5
D6
D5
Slot C
long case
fuse
Power
power
power
98
99
CF
CD
CE
B5
D6
D5
Slot C
short case
fuse
• Minimum/Maximum Ratings
• 85 to 264V
Å
(ac)
• 20.4 to 26.4 V
ı
(ac/dc)
• 47 to 63Hz
• 6VA maximum
Standard Bus EIA-485 Communications
Standard Bus
EIA-485
T-/R-
common
98
99
CF
CD
CE
B5
D6
D5
Slot C
long case
T+/R+
Standard Bus
EIA-485
T-/R-
common
98
99
CF
CD
CE
Slot C
short case
T+/R+
• Wire T-/R- to the A terminal of the EIA-485 port.
• Wire T+/R+ to the B terminal of the EIA-485 port.
• Wire common to the common terminal of the EIA-485
port.
• Do not route network wires with power wires. Connect
network wires in daisy-chain fashion when connecting
multiple devices in a network.
• Do not connect more than 16 controllers on a network.
• maximum network length: 1,200 meters (4,000 feet)
• 1/8th unit load on EIA-485 bus
Note:
Disconnect any USB to EIA-485 converter when not
connected to a PC (without power). Failure to do so
may cause communications errors.
EIA-232/485 Modbus RTU Communications
485 common
485 T+/R+
CB
CA
CC
CB
CA
C5
C3
C2
Slot B
485 T-/R-
485 T+/R+
485 T-/R-
232 common
232 (TX) to DB9 pin 2 (RD)
232 (RD) to DB9 pin 3 (TX)
• Wire T-/R- to the A terminal
of the EIA-485 port.
• Wire T+/R+ to the B termi-
nal of the EIA-485 port.
• Wire common to the com-
mon terminal of the EIA-
485 port.
• Do not route network wires
with power wires. Connect
network wires in daisy-
chain fashion when connect-
ing multiple devices in a
network.
• A termination resistor may
be required. Place a 120 Ω
resistor across T+/R+ and
T-/R- of last controller on
network.
• Do not wire to both the EIA-
485 and the EIA-232 pins at
the same time.
• Two EIA-485 terminals of
T/R are provided to assist in
daisy-chain wiring.
• Do not connect more than
one EZ-ZONE
®
RUI on a
EIA-232 network.
• Maximum number of EZ-
ZONE
®
RUI on a Modbus
®
RTU EIA-485 network: 247
• Maximum EIA-232 network
length: 15 meters (50 feet)
• Maximum EIA-485 network
length: 1,200 meters (4,000
feet)
• 1/8th unit load on EIA-485
bus.
EZK _-_ 2 _ _-A _ A A
Modbus-IDA
Terminal
EIA/TIA-485
Name
Watlow Termi-
nal Label
Function
DO
A
CA or CD
T-/R-
D1
B
CB or CE
T+/R+
common
common
CC or CF
common
Note:
Disconnect any USB to EIA-485 converter when not connected to a PC
(without power). Failure to do so may cause communications errors.