Watlow EZ-ZONE

®

RUI/Gateway

24

Chapter 4 RUI Page

Display

Parameter name

Description

Range

Default

Modbus

Relative Ad-

dress

CIP

Class

Instance

Attribute

hex (dec)

Profibus

Index

Param-

eter ID

Data

Type

& Read/

Write

[iP;g2]
[ip.g2]

Communications 2

IP Fixed Gateway Part 2

Set the router IP address for

the remote network.

0 to 255

0

- - - -

- - - -

- - - -

17027

uint

RW

[iP;g3]
[ip.g3]

Communications 2

IP Fixed Gateway Part 3

Set the router IP address for

the remote network.

0 to 255

0

- - - -

- - - -

- - - -

17028

uint

RW

[iP;g4]
[ip.g4]

Communications 2

IP Fixed Gateway Part 4

Set the router IP address for

the remote network.

0 to 255

0

- - - -

- - - -

- - - -

17029

uint

RW

[iP;g5]
[ip.g4]

Communications 2

IP Fixed Gateway Part 5

Set the router IP address for

the remote network.

0 to 255

0

- - - -

- - - -

- - - -

17030

uint

RW

[iP;g6]
[ip.g4]

Communications 2

IP Fixed Gateway Part 6

Set the router IP address for

the remote network.

0 to 255

0

- - - -

- - - -

- - - -

17031

uint

RW

[Mb;E]
[Mb.E]

Communications 2

Modbus TCP Enable

Activate Modbus TCP.

[``no]

No

[`YES}

Yes

Yes

- - - -

- - - -

- - - -

17041

uint

RWE

[EiP;E]
[EiP.E]

Communications 2

EtherNet/IP™ Enable

Activate Ethernet/IP™.

[``no]

No

[`YES}

Yes

Yes

- - - -

- - - -

- - - -

17042

uint

RWE

[`Ad;d]
[ Ad.d]

Communications 2

DeviceNet™ Node Address

Set the DeviceNet™ address

for this gateway.

0 to 63

63

- - - -

- - - -

- - - -

17052

uint

RWE

[bAUd]
[bAUd]

Communications 2

Baud Rate DeviceNet™

Set the speed of this gate-

way's communications to

match the speed of the serial

network.

[`125]

125 kb

[`250]

250 kb

[`500]

500 kb

125

- - - -

- - - -

- - - -

17053

uint

RWE

[`FC;E]
[ FC.E]

Communications 2

DeviceNet™ Quick Con-

nect Enable

Allows for immediate com-

munication with the scanner

upon power up.

[``no]

No

[`YES}

Yes

No

- - - -

- - - -

- - - -

17054

uint

RWE

[p;add]
[P.Add]

Communications 2

Profibus Address

Set the Profibus DP address

for this gateway.

[``no]

No

[`YES}

Yes

No

- - - -

- - - -

- - - -

17060

uint

RWE

[a;loc]
[A.Loc]

Communications 2

Profibus DP address lock

When set to yes will not al-

low address to be changed

using software. Can be

changed from front panel.

[``no]

No

[`YES}

Yes

No

- - - -

- - - -

- - - -

17061

uint

RWE

[`C_F]
[ C_F]

Communications 2

Display Units

Select which scale to use for

temperature passed over

communications port 2.

[```f]

F

[```C}

C

F

440

0x96 (150)

2

6

25

17050

uint

RWE

Advertising